Which of the following statements is incorrect when
describing a deluge system? - ANSWER-Deluge system
detection devices should be automatically supervised.
Deluge systems are required to be automatically
supervised.
Reference NFPA 13 2016, Sections 3.4.4, 7.3.3.1 and
7.3.3.2.
,Choose all that apply to a Dry Pipe System - ANSWER-1.
Require approved pressure gauges on the water side of
the dry pipe valve.
2. Permit Horizontal sidewall sprinklers to be installed so
that water is not trapped.
3. Shall protect the dry pipe valve and supply pipe from
freezing and mechanical damage.
Reference NFPA 13 2016, Sections 7.2.1, 7.2.2 and
7.2.5.1.
This pump is characterized by a method of producing flow
by capturing a specific volume of fluid per pump revolution
and reducing the fluid void by a mechanical means to
,displace the pumping fluid: - ANSWER-Positive
Discplacement Pump
Refrence NFPA 20 2016 Section 3.3.44.14.
Which of the following sprinklers produces large water
droplets and is listed for its capability to provide fire control
of specific high-challenge fire hazards? - ANSWER-CMSA
Sprinkler
Refrence 13 2016
Section 3.6.4.2.
, A standpipe system with no permanently attached water
supply that relies exclusively on the fire department
connection to supply the system demand. - ANSWER-
Manual Dry
Reference NFPA 14 2016
Section 3.3.17.4.
For corrosive water conditions, steel pipe on the suction
side of the pump is required to be: - ANSWER-Galvanized
or painted on the interior with a paint recommended for
submerged surfaces
Refrence NFPA 20 2016