1. what is the maximum number of 14 AWG RHH conductors which can be
installed in 1/2 rigid metal conduit?
Answer 4 wires
2. Which of the following would be an appropriate mounting height for a pull
station?
Answer 3.5'-48" to the actuator
3. What is the minimum flash rate for a visible notification device?
Answer 1 flash per second
4. What is the minimum mounting height for audible notification devices?
Answer 90" to the top of the device
5. What is the minimum mounting height for visible notification devices?
Answer Such that the entire lens is not less then 80"
6. What is the formula for Ohm's Law
Answer Voltage=Current X Resistence
7. When using your mult-meter to measure, you must
Answer Put your meter in series with the circuit
1/
14
, 8. Waterflow devices shall be tested with that frequency?
Answer Semi-annually
9. With what frequency shall ionization smoke detectors be given a functional
test?
Answer Annually
10. What are the standby power requirements for a proprietary signaling
sys- tem?
Answer 24 hours in normal operation, 5 minutes in alarm
11. Which of the following is a type of auxiliary protective signaling system?
Answer Shunt type
12. Remote station signaling systems are permitted to send signals to
Answer A UL listed central station
A receiver located at an unlisted monitoring facility A
fire department or communications center
13. Non-power limited fire alarm cable shall have an insulation rating of
Answer 600V
14. Which of these HVAC systems would require duct detectors on supply
and return?
2/
14