1. A factory Uses a motorized gate opener for access to there facility. The fire
alarm panel uses an on-board relay to open the gate upon alarm, What
operation or signal is required of this circuit should an open occur? (broken
wire to gate opener)? - ANSWER Trouble signal or gate operation would
occur.
2. The _______ is/are responsible for keeping all installation documents
related to their installations. - ANSWER System Owner
3. Inspections, testing, or maintenance shall be permitted to be done by a
person or organization other then the owner if___________. - ANSWER
Conducted under a written contract.
4. Who is responsible for the inspection, testing and maintenance of the fire
alarm system? - ANSWER The Owner
5. When are visual alarm notification devices required to be tested? - ANSWER
During the acceptance test and annually thereafter.
,6. While performing regularly scheduled testing of a fire alarm system, you
discover that it is impaired. Who does NFPA 72 require you to notify? -
ANSWER The system owner of their designated representative.
7. Which of the following best describes how often a spot type smoke
detector should be tested for sensitivity using a calibrated test method. -
ANSWER After one year and every alternate year thereafter.
8. What is the required test frequency for a pressure-type water flow initiating
device? - ANSWER Semiannually.
9. During an annual test of a fire alarm system, you simulate a detectors
operation. On the inspection record you must now________. - ANSWER
Indicate which device (Location and Type) was simulated.
10.How often must household fire alarm system smoke detectors be tested by
a qualified alarm tech? - ANSWER Never the home owner can do this.
11.While testing a fire alarm system you remove a two-wire smoke detector
from its plug-in base on a Class B type circuit. What alarm capability would
you expect from the other detectors on that circuit? - ANSWER
Activated detectors between the control unit and that detector base should
alarm.
, 12.If a defect or malfunction is not corrected at the conclusion of system
inspection, testing, or maintenance, the responsible party shall be informed
of the impairment _______. - ANSWER In writing, within 24 hours
13.When testing a water level supervisory switch serving a pressurized water
storage tank, a signal must be indicated whenever the water_______ from
the normal level. - ANSWER rises or falls 3 inches
14.NFPA 72 requires that the fire alarm contractor complete all portions of the
record of completion_________. - ANSWER for the portion of the
system for which they had responsibility.
15.Where must the record of completion be kept? - ANSWER In a
document Cabinet.
16.What is the required testing frequency of a radiant energy type fire
detector? - ANSWER Semiannually.
17.All fire alarm service personnel shall be qualified and ___________. -
ANSWER experienced
18.Installation personnel shall be qualified or shall be supervised by persons
who are qualified in the installation inspection and testing of fire alarm
systems. Qualified personnel shall include, but not be limited to, three of
the following groups: ______________ - ANSWER "Personnel who are
certified by a nationally recognized fire alarm certification organization
acceptable to the AHJ.Personnel who are registered, licensed, or certified