1. A fire alarm system that is connected to a municipal fire alarm system for
transmitting a fire alarm to the public fire service communications center is
what type?
A. Auxiliary fire alarm
B. Local fire alarm system
C. Protected premises fire alarm system
D. Remote fire alarm system
E. Central station fire alarm system
- ANSWER Auxiliary fire alarm system
2. The three-pulse temporal evacuation signal must be used __________.
A. In place of a prerecorded voice announcement
B. For notification of the need to evacuate the building or relocate within a
building
C. To notify the need to remain inside a building
D. During a supervisory condition
E. The three-pulse temporal signal cannot be used in a fire alarm system
- ANSWER For notification of the need to evacuate the building or relocate
within a building
, 3. When is synchronization of the three-pulse temporal evacuation signal
required?
A. In private mode signaling only
B. On all devices within the same building
C. On all devices that share the same notification zone
D. In all devices in the entire system
E. Never
- ANSWER On all devices that share the same notification zone
4. Which element is NOT required to be provided for a fire alarm system
installed for central station service?
A. Engineering
B. Installation of fire alarm transmitters
C. Retransmission
D. Testing and maintenance
E. Runner service
- ANSWER Engineering
5. What is the recommended coded signal for the basement of a four-story
building?
A. 1-1
B. 1-2
C. 2-1
D. 2-2
E. 3-1
- ANSWER 3-1
, 6. Which of the following devices would send a signal not considered a
supervisory signal?
A. Line-type heat detector
B. Water level indicator
C. Low air pressure switch
D. Valve switch
E. Guard tour station
- ANSWER Line-type heat detector
7. After what period of time is a guard considered delinquent after failing to
actuate a tour station device as scheduled?
A. 3 minutes
B. 5 minutes
C. 8 minutes
D. 10 minutes
E. 15 minutes
- ANSWER 15 minutes
8. Control valve supervisory signals indicating an off-normal condition must be
initiated ________.
A. During the first 2 turns of a hand wheel
B. During the first 1/5 travel distance of the valve control apparatus
C. During the first 1/5 turn of a hand wheel
D. Both A and B
E. Both A and C
- ANSWER Both A and B
A. During the first 2 turns of a hand wheel
B. During the first 1/5 travel distance of the valve control apparatus
, 9. Elevator control interfaces, door release mechanisms, HVAC shutdown
smoke detectors, exit marking appliances, and door unlocking devices fall
under the heading of what?
A. Supervisory functions
B. Trouble functions
C. Emergency control functions
D. Alarm functions
E. Supervising station functions
- ANSWER Emergency control functions
10. Within what period of time must a single open or single ground fault
condition on a fire alarm system's wiring be automatically indicated?
A. 30 seconds
B. 60 seconds
C. 90 seconds
D. 150 seconds
E. 200 seconds
- ANSWER 200 seconds
11. Automatic closing of smoke control doors directly from a smoke detector
may only be done by _________?
A. Ceiling mounted smoke detectors
B. Dedicated smoke detectors placed at or near the doors
C. Duct detectors serving the air space
D. Relay based smoke detectors
E. Smoke detectors specially listed for releasing service