and Conceptual Actual Frequently Tested
Exam Questions With Reviewed 100%
Correct Detailed Answers
Guaranteed Pass!!Current Update!!
1. If a fire alarm system requires software, who should receive a copy of the
software?
a. The system owner
b. The AHJ
c. The fire department
d. The monitoring company - ANSWER a. The system owner
2. Manual fire alarm boxes shall be ______ in color.
a. Red
b. Green
c. Blue
d. Black - ANSWER a. Red
3. When a non-restorable fixed temperature line type heat detector is tested
annually, the testing records shall be kept by....
a. The AHJ
,b. The monitoring Company
c. The contractor
d. The system owner - ANSWER d. The system owner
4. To test a water temperature switch, the switch shall be operated and receipt of
signal hall be verified to indicate the decrease in water temperature to ---- degrees
F and its restoration to above ____ degrees F.
a. 40/50
b. 32/85
c. 32/40
d. 40/40 - ANSWER d. 40/40
5. After a fire alarm system is installed, where should the record documentation
be stored?
a. At the local fire department
b. At any location
c. In a document cabinet at the protected premises.
d. At an offsite location owned by the building owner. - ANSWER c. In a
document cabinet at the protected premises.
6. How should fixed-temperature, non-restorable line type heat detectors be
tested?
a. Do not perform heat test. Test functionally mechanically and electrically
b. Test prescribed to manufactures method
,c. Verify correct operation by removal of the fusible link
d. Perform heat test with a listed and labeled heat source. - ANSWER a. Do not
perform heat test. Test functionally mechanically and electrically
7. Duct type smoke detectors shall be tested ________.
a. Monthly
b. Semiannually
c. Annually
d. According to AHJ - ANSWER c. Annually
8. A heat detector with a listed spacing of 50 feet will be installed. What spacing
shall be used for a 20 foot ceiling that is smooth and flat?
a. 29 feet
b. 32 feet
c. 35.2 feet
d. 40 feet - ANSWER b. 32 feet
9. Smoke detectors that have provision for field adjustment of sensitivity shall
have an adjustment range of ________ per foot obstruction.
a. Not more than 0.7%
b. Not more than 0.6%
c. Not less than 0.7%
d. Not less than 0.6% - ANSWER d. Not less than 0.6%
, 19. A sloping ceiling is a ceiling that has a slop of more than _______.
a. 1 in 8
b. 1 in 7
c. 1 in 6
d. None of the above - ANSWER a. 1 in 8
20. Manual fire alarm boxes shall be located within ______ of the exit doorway.
a. 4 feet
b. 4 feet, on the outside of the doorway
c. 5 feet
d. 5 feet, on the inside of the doorway. - ANSWER c. 5 feet
21. The fire alarm circuit disconnect shall be permitted to be secured in the ____
position.
a. on
b. off
c. middle
d. down - ANSWER a. on
22. When installing fire alarm cables, which of the following methods of support
is acceptable?
a. Strap the cables to a nearby conduit