Installation & Maintenance
The point of transfer at a dispensing unit must be ____ from Public ways, including public streets,
highways, thoroughfares, and sidewalks.
A. 10 feet
B. 15 feet
C. 25 feet - ✔✔ correct answer A. 10 feet
Steel supports on vertical ASME containers shall be protected against fire exposure with a material
having a fire resistance rating of a least _____, except that continuous steel skirts that have only one
opening that is 18 in. or less in diameter shall have fire protection applied to the ______ of the skirts.
A. 3 hrs; outside
B. 2 hrs; outside
C. 3 hrs; inside - ✔✔ correct answer B. 2 hrs; outside
Pressure relief devices installed in underground containers serving dispensing systems shall be piped
vertically upward to a point at least _____ above the ground.
A. 2 feet
B. 6 feet
C. 10 feet - ✔✔ correct answer C. 10 feet
A remote emergency shut off device for either the internal valve or emergency shutoff valve is
required to be located not less than _____ or more than _____ from the liquid transfer point.
A. 10 ft ; 50ft
B. 10 ft; 100ft
C. 3 ft; 100ft - ✔✔ correct answer C. 3 ft; 100ft
The markings for the switch or circuit breaker to shut off power in an emergency shall be visible from
________.