2025-2026. Questions and Correct
Verified Answers. Graded A
All extinguishment systems with automatic detection equipment for
activation shall also have...? - ANSMeans for manual activation (pull
station)
All systems shall test free of BLANK except for applications in which
BLANK are approved. - ANSGrounds, grounds
Any device intended to lock or unlock the exits shall be BLANK -
ANSConnected to the fire alarm system
As the mounting location of smokes and heats gets higher, the listed
spacing must be reduced. True or False? - ANSFalse. The higher a heat is
positioned, the smaller the spacing. The higher a smoke is positioned, the
wider the spacing.
Average ambient sound levels greater than BLANK shall require the use of
BLANK. - ANS95db, Visual notification appliances
Before proceeding with any testing, who must be notified and why? -
ANSFacilities receiving the alarm and all building occupants. The purpose
is to avoid unnecessary response.
, Can a detector be installed during construction? - ANSNo, unless they are
replaced after all construction is complete.
Can detectors be installed within an air duct system? Can they be used as
a substitute for open area protection? - ANSYes. And no.
Conductors of 26AWG shall only be permitted in which circumstances? -
ANSWhere spliced with a connector listed as suitable for 26 to 24 AWG
Detectors and appliances can be mounted using wires behind them. True
or False? - ANSFalse. All detectors and appliances must be secured
independently of their wiring.
Detectors and appliances shall be protected from damage by a mechanical
guard as long as. .. ? - ANSIt is listed for the purpose and does not
interfere with the operation of the device.
Detectors shall be BLANK for the purpose for which they are being used. -
ANSListed (i.e. UL Listed)
Does a fire hood sprinkler system in a kitchen need to be monitored by the
fire alarm system? - ANSYes
Does an exterior horn for a sprinkler system need to be supervised? -
ANSYes