| All Questions and Correct Answers | Verified
Answers | Graded A+ | Just Released
Capable of being reached for operation, renewal, and inspection is known as
what?
A. accessible (regarding equipment)
B. accessible (regarding wiring methods)
C. accessible (regarding termination)
D. accessible (regarding FACP) ---------CORRECT ANSWER-----------------A
After acceptance testing, what type of drawings are required to be presented to
the building owner?
A. As Built Drawings
B. Contract Drawings
C. Point-To-Point Diagrams
D. Manufacturer's Drawings ---------CORRECT ANSWER-----------------A
According to the IBC, strobe lights/appliances shall not be required in
________________ ? ---------CORRECT ANSWER-----------------Elevator Cars
,According to the IBC, which of the following fire alarm systems are required in a
Group F occupancy?
A. a manual and automatic fire alarm system with occupant notification.
B. an automatic fire alarm system without occupant notification
C. a manual fire alarm system without occupant notification.
D. a manual fire alarm system with occupant notification ---------CORRECT
ANSWER-----------------D
Conductorrs of shunt circuits shall not be smaller than ______________ and shall
be ____________.
A. 14 AWG / Insulated
B. 18 AWG / Insulated
C. 14 AWG / Covered
D. 18 AWG / Covered ---------CORRECT ANSWER-----------------14 AWG
A bar chart intended for displaying simple events plotted against time or dollars. -
--------CORRECT ANSWER-----------------Gantt Chart
In Project Management, the Arrow Diagram Method is also known as the
_________ ? ---------CORRECT ANSWER-----------------Critical Path Method
,According to the IBC, a manual fire alarm system is NOT required to be installed in
Group A occupancies where ___________
A. the occupant load due to the assembly occupancy is less than 300
B. the building is equipped with an automatic fire alarm system
C. The occupant load due to the assembly occupancy is 300 or more
D. None of the above. ---------CORRECT ANSWER-----------------A
A fire alarm technician updated the programming of the fire alarm control unit.
The changes did not affect any initiating devices connected to theh system. Is the
technician responsible, as per NFPA 72, for testing and correcting any of these
(unaffected) initiating devices? If so, what percentage? ---------CORRECT ANSWER-
----------------Yes, 10%
In a dry-pipe sprinkler system, the off-normal signal initiation requirement shall
signal when the pressure increases or decreases by _____________ psi ---------
CORRECT ANSWER-----------------10 psi
According to the NFPA 72, a corridor adheres to the requirements of a room
when the corridor is wider than __________ feet ---------CORRECT ANSWER---------
--------20 feet
In Group I-1 occupancies, an automatic smoke detection system shall be installed
in __________________ (choose 2)
, A. Corridors
B. Sleeping Units
C. Kitchens
D. Waiting Areas ---------CORRECT ANSWER-----------------A and D
When an occupancy with an atrium connects more than ______________ stories,
a fire alarm system shall be installed with smoke detection throughout the
building. ---------CORRECT ANSWER-----------------2 stories
True or false: A corridor that is 20 feet in width adheres to the spacing
requirements of a room. ---------CORRECT ANSWER-----------------False
A fire alarm system was installed in a building, which by all applicable codes, does
not require a fire alarm system. Which of the following statements is true?
A. The fire alarm system and its components shall fully comply with the
requirements of NFPA 72
B. The fire alarm system is a non-required system. It need not comply with NFPA
72
C. The fire alarm system is not allowed by code.
D. None of the above. ---------CORRECT ANSWER-----------------A