Review | 92
Comprehensive Test Questions
and Verified Answers | 100%
Correct | Grade A (Newest
Update)
Quiz_________________?
Under which of these conditions shall the instrument Air Reserve header
cylinders be permitted to be stored with the instrument air compressor?
A) the mechanical equipment room does not contain a boiler.
B) the medical air compressors are in the same room.
C) the only motor-driven machinery in the room is for instrument air
equipment.
D) the room is secured with lockable doors. -
Answer☑️
C) The only motor-driven machinery in the room is for the instrument air
equipment
Quiz_________________?
Riser valves are those valves located where?
A) adjacent to the main riser downstream of any zone valve.
B) anywhere in the lateral branches of the piping system.
C) in the mainline adjacent to the base of the riser.
D) in the riser adjacent to the mainline. -
Answer☑️
D) In the riser adjacent to the main line
1
, Quiz_________________?
When is the initial pressure test conducted by the installer?
A) after blowdown of the distribution piping.
B) after installation of alarm sensors.
C) before blowdown of distribution piping.
D) before installation of station rough in assembly. -
Answer☑️
A) After blow-down of the distribution piping.
Quiz_________________?
In those portions of systems intended to handle oxygen at pressure greater
than 350 psi the inter connecting hose shall not contain what materials?
A) brass.
B) copper
C) polymeric
D) stainless steel -
Answer☑️
C) Polymeric
Quiz_________________?
The tool shown here allows the installer to mechanically limit the makeup
depth of the fitting to be brazed. Under what condition is this method
permitted for the installation of medical gas piping?
A) only on final line connectors.
B) only on vacuum systems.
C) where only B cup 5 brazing rod is used
D) where the limited makeup depth is not less than minimum cut depth her
ANSI / ASME recommendations -
Answer☑️
D) Where the limited makeup depth is not less than minimum cup depth
current ANSI\ASME recommendation
Quiz_________________?
What is the standard gauge pressure for nitrogen gas service?
A) 15 - 30
B) 50 - 55
C) 162 185
D) it varies with system type. -
2
, Answer☑️
C) 50 - 55 psi
Quiz_________________?
What is a NFPA 99 requirement for labeling of pipes in medical gas
system?
A) color coding
B) fixed label with
C) label shall wrap completely around pipe.
D) reflective label -
Answer☑️
A) Color coding
Quiz_________________?
A wireless communication device is employed in a medical gas or vacuum
warning system. what type of supervision is required for this device?
A) a visual indicator Shelby located in maintenance officer or engineering
department.
B) this device shall be installed at the medical gas or vacuum source.
C) this device shall be located at nurses station.
D) this device will be supervised such that failure communication shall
initiate an alarm. -
Answer☑️
D) This device will be supervised such that failure of communication shall
initate an alarm
Quiz_________________?
In a facility where Medical Gas vacuum systems are present and the failure
of such equipment or systems is likely to cause any major injury or death to
patients or caregivers this system shall be designed to meet which
category requirements?
A) 1
B) 2
C) 3
D) 4 -
Answer☑️
A) category 1
Quiz_________________?
3