How Many Grounds Should Be Placed Within 1 Mile - Answers-4
What Is The Typical Size Of A Driven Ground Rod - Answers-5/8 Or
3/4 Inch Metal
Doubling The Length Of The Ground Rod Wil Typically Reduce
Resistance By - Answers-40%
Doubling The Diameter Of The Ground Rod Wil Typically Reduce
Resistance By - Answers-10%
True Or False
Some Companies Allow Anchor Rodes To Be Used As A Ground
Source Due To Their Depth And Availability Throughout The System -
Answers-True
What Must Be Done Before The Start Of Any Job - Answers-Job
Briefing
True Or False
END OF
PAGE
1
, SLTC FINAL EXAM LATEST
It Is Not A Osha Requirement To Lock And Tag All Switches -
Answers-Fasle
What Is To Be Down Directly Before Applying Grounds - Answers-Test
Is It A Osha Requirement To Test The Line Before Applying Grounds -
Answers-Yes
What Are Two Categories Of Grounding Clamps - Answers-'C' Clamps
And 'Snap-On' Clamps
True Or False
As A General Rule, The Length Of Grounds Should Be Kept As Short
As Possible - Answers-True
Personal Protective Grounding Cables Must Never Be Smaller Than
What - Answers-#2 Awg Copper
In Epz Grounds, What Provides Contact To The Pole Which Establishs
The Zone - Answers-Cluster Bracket
END OF
PAGE
2
, SLTC FINAL EXAM LATEST
What Is A Effective Way To Protect The Lineworker While Stringing
Wire - Answers-Run Ground Devices
Golden Rule For Grounding - Answers-Always Connect The Ground
Source First The To The Conductor With Live Line Tools
How To Clean Grounding Connections - Answers-Wire Brush
T/F: Osha Requires You Use Live Line Tools To Install And Remove
Personal Protective Grounding - Answers-True
Common Conditions That Cause Grounds To Fail - Answers-1. Loose
Connections
2. Corroded Connections
3. Corroded Clamp Jaws
4. Moisture And Road Salt Intrusion In The Cable
5. Improper Crimping Of The Ferrule
T/F: Osha Does Not Require The Grounding Of Vehicles - Answers-
True
END OF
PAGE
3
, SLTC FINAL EXAM LATEST
They Recommend You Ground The Vehicle Or Blockade
Osha Requires You Wait How Long After De-Energizing A Capacitor -
Answers-5 Minutes
Underground Circuits Are Designed With What Kind Of Front -
Answers-Dead Front
T/F: With Underground Circuits The Ground Source Is Readily
Available - Answers-True
Portable Feed Through Is Used To - Answers-Isolate Test And Ground
Personal Protective Grounding Conductors For Underground Lines And
Equipment Must Never Be Smaller Than - Answers-#2 Awg Copper
Fully Rated For Fault Current - Answers-Grounding Elbow
Puprose Of The Rubber Cap On Dead Front Equipment - Answers-
Insulates, Shields, And Seals
END OF
PAGE
4