BRANCH CIRCUITS EXAM QUESTIONS AND ANSWERS LATEST
DOWNLOADED 2025/2026 A COMPLETE SOLUTION ALL ANSWERS
100% CORRECT VERIFIED BEST GRADED A+ FOR SUCCESS
Which NEC reference covers the means of identifying grounded conductors?
a.
90.5
b.
110.3
c.
200.6
d.
210.4(A) - CORRECT ANSWERS 200.6
The branch-circuit conductors for a household electric range rated in excess of 8 3/4 kilowatts
shall generally have a rating of not less than ? .
a. 15 A
b. 20 A
c. 30 A
d. 40 A - CORRECT ANSWERS 40A 210.19(A)(3)
A duplex receptacle is a single receptacle, by definition
T/F - CORRECT ANSWERS false 100
Receptacles rated 15 amperes are permitted to be installed on both 15- and 20-ampere branch
circuits.
T/F - CORRECT ANSWERS True 210.21(B)(2), Table 210.21(B)(2), 210.21(B)(3), Table
210.21(B)(3), 210.24, and Table 210.24.
, CODE, STANDARDS, AND PRACTICES 2, LEVEL I-2020 LESSON 2:
BRANCH CIRCUITS EXAM QUESTIONS AND ANSWERS LATEST
DOWNLOADED 2025/2026 A COMPLETE SOLUTION ALL ANSWERS
100% CORRECT VERIFIED BEST GRADED A+ FOR SUCCESS
What is the maximum load, in amperes, permitted to be cord-and-plug-connected to a 20-
ampere multi-outlet branch circuit?
a. 12 A
b. 16 A
c. 20 A
d. 24 A - CORRECT ANSWERS 16A 210.23(A)(1)
The maximum rating of a cord-and-plug-connected appliance to a 30-ampere branch circuit
with more than one outlet is 24 amperes.
T/F - CORRECT ANSWERS True 210.23(A)(1)
The permissible load, in amperes, for an appliance fastened in place and connected to a 20-
ampere branch circuit that also feeds lighting outlets and cord-and-plug-connected equipment
is ?
a. 5 A
b. 10 A
c. 15 A
d. 20 A - CORRECT ANSWERS 10A 210.23(A)(2)
A two-family dwelling contains a single branch circuit that supplies a lighting circuit for common
areas and outside lighting. The branch circuit originates from a panelboard located in dwelling
unit No. 1.
A. Acceptable
B. Violation - CORRECT ANSWERS Violation 210.25(B)
The basic rule(s) for connecting utilization equipment to multiwire branch circuits generally
permits ? .