Terms in this set (269)
What is the preferred method of Use of the manufacturer's test kit or rewiring the neutral CT input is the preferred
performing primary-injection testing on a method of primary-injection testing on a low voltage circuit breaker with ground
low voltage circuit breaker with ground fault protection, otherwise two poles can be connected in series to provide
fault protection? balanced secondary currents to the trip unit.
At what current level does ventricular -60 to 100mA in AC systems
fibrillation occur? -300 to 500mA in DC systems
For a 70kg body
What is the LET-GO current threshold? 75mA DC
15mA AC
Meter Sockets and meter disconnect FALSE
switches should be connected on the load (NEC Article 230.82)
side of a service disconnecting means.
Which standard addresses equipment NFPA 70 (National Electric Code)
grounding?
A moving iron meter operates by applying Operating current ( can be AC or DC)
_____ current to the coil.
What is the maximum deviation between 50% of the lowest value
resistance measurements on bolted (MTS 7.20.3.1)
connections?
Identify the electrical symbol shown:
Removable / Drawout circuit breaker
Normally 5kV or above
Resistance grounding is used for voltages: 6.6kV and greater
https://quizlet.com/457015131/neta-level-ii-exam-flash-cards/ 1/7
, 10/5/25, 9:53 AM NETA level II exam Flashcards | Quizlet
Blowout coils may be used to extinguish the arc by means of a magnetic blast. The
arc created when the contacts open is subjected to the action of a magnetic field set
Medium-voltage motor starters use up by coils connected in series with the circuit being interrupted.
blowout coils. What do these do? These coils are called blowout coils because they help blow out the arc
magnetically. The arc is magnetically blown into arc chutes where the arc is
lengthened, cooled, and extinguished.
Puffer tubes incorporate the operating mechanism to blow a puff of air through a
Medium voltage air circuit breakers use
tube and nozzle to each contact assembly when the breaker is opened. The air helps
PUFFER TUBES. What do these do?
quench the arc by pushing it up into the arc-chute.
Identify the electrical symbol shown:
Ammeter
No lines on head
SAE grade 1 & 2 Bolt
Tensile strength 64KSI
3 lines on head
SAE grade 5 Bolt
Tensile strength 105 KSI
5 lines on head
SAE grade 7 Bolt
Tensile strength 133 KSI
6 lines on head
Tensile strength 150 KSI
SAE grade 8 Bolt
(Non-serviceable) - Device has a problem detrimental to its proper electrical or
NFPA 70B 11.27.3 Decal color code RED mechanical operation such as no trip on one or more phases or high contact
resistance readings. This device should not be placed back into service.
(Limited Service) - Device has a minor problem that does not impact equipment
serviceability but should be fixed as soon as possible. Some examples of minor
NFPA 70B 11.27.3 Decal color code yellow
problems include slightly lower than acceptable insulation resistance readings or
chipped arc chutes.
(Servicable) - Device is electrically and mechanically sound and suitable for service
NFPA 70B 11.27.3 Decal color code white
but may still have minor defects such as slight corrosion or incorrect circuit ID.
What instructions govern the ANSI/IEEE standard 399
performance of a SHORT CIRCUIT Step by step procedures outlined in the short circuit calculation chapters of IEEE
STUDY? standard 141 and ANSI/IEEE 242.
ANSI/IEEE STANDARD 399
What instructions govern the
ANSI/IEEE STANDARD 242
performance of a Coordination STUDY?
NFPA 70 (NATIONAL ELECTRIC CODE) protective devices
Two standards are typically used for the IEEE C37.1
interconnection of smart devices in a IEC 61850
substation environment. One is an IEC
standard, the other is an IEEE standard.
What are the two standards?
Time travel analysis is commonly is used on medium and high-voltage circuit breakers and provides information as to
performed on: whether the breaker's operating mechanism is operating properly (NFPA 70B).
https://quizlet.com/457015131/neta-level-ii-exam-flash-cards/ 2/7
Science Engineering Electrical Engineering
NETA level II exam
7 studiers in 3 days 4.0 (1 review)
Save
Students also studied
Flashcard sets Study guides Practice tests
Ohms Law Grounding and Bounding RADX PHYS unit 2 exam ENGR 2
7 terms 42 terms 45 terms 12 terms
gracedixon361 Preview Steven_Shilliday Preview mya_simmons05 Preview mru
Terms in this set (269)
What is the preferred method of Use of the manufacturer's test kit or rewiring the neutral CT input is the preferred
performing primary-injection testing on a method of primary-injection testing on a low voltage circuit breaker with ground
low voltage circuit breaker with ground fault protection, otherwise two poles can be connected in series to provide
fault protection? balanced secondary currents to the trip unit.
At what current level does ventricular -60 to 100mA in AC systems
fibrillation occur? -300 to 500mA in DC systems
For a 70kg body
What is the LET-GO current threshold? 75mA DC
15mA AC
Meter Sockets and meter disconnect FALSE
switches should be connected on the load (NEC Article 230.82)
side of a service disconnecting means.
Which standard addresses equipment NFPA 70 (National Electric Code)
grounding?
A moving iron meter operates by applying Operating current ( can be AC or DC)
_____ current to the coil.
What is the maximum deviation between 50% of the lowest value
resistance measurements on bolted (MTS 7.20.3.1)
connections?
Identify the electrical symbol shown:
Removable / Drawout circuit breaker
Normally 5kV or above
Resistance grounding is used for voltages: 6.6kV and greater
https://quizlet.com/457015131/neta-level-ii-exam-flash-cards/ 1/7
, 10/5/25, 9:53 AM NETA level II exam Flashcards | Quizlet
Blowout coils may be used to extinguish the arc by means of a magnetic blast. The
arc created when the contacts open is subjected to the action of a magnetic field set
Medium-voltage motor starters use up by coils connected in series with the circuit being interrupted.
blowout coils. What do these do? These coils are called blowout coils because they help blow out the arc
magnetically. The arc is magnetically blown into arc chutes where the arc is
lengthened, cooled, and extinguished.
Puffer tubes incorporate the operating mechanism to blow a puff of air through a
Medium voltage air circuit breakers use
tube and nozzle to each contact assembly when the breaker is opened. The air helps
PUFFER TUBES. What do these do?
quench the arc by pushing it up into the arc-chute.
Identify the electrical symbol shown:
Ammeter
No lines on head
SAE grade 1 & 2 Bolt
Tensile strength 64KSI
3 lines on head
SAE grade 5 Bolt
Tensile strength 105 KSI
5 lines on head
SAE grade 7 Bolt
Tensile strength 133 KSI
6 lines on head
Tensile strength 150 KSI
SAE grade 8 Bolt
(Non-serviceable) - Device has a problem detrimental to its proper electrical or
NFPA 70B 11.27.3 Decal color code RED mechanical operation such as no trip on one or more phases or high contact
resistance readings. This device should not be placed back into service.
(Limited Service) - Device has a minor problem that does not impact equipment
serviceability but should be fixed as soon as possible. Some examples of minor
NFPA 70B 11.27.3 Decal color code yellow
problems include slightly lower than acceptable insulation resistance readings or
chipped arc chutes.
(Servicable) - Device is electrically and mechanically sound and suitable for service
NFPA 70B 11.27.3 Decal color code white
but may still have minor defects such as slight corrosion or incorrect circuit ID.
What instructions govern the ANSI/IEEE standard 399
performance of a SHORT CIRCUIT Step by step procedures outlined in the short circuit calculation chapters of IEEE
STUDY? standard 141 and ANSI/IEEE 242.
ANSI/IEEE STANDARD 399
What instructions govern the
ANSI/IEEE STANDARD 242
performance of a Coordination STUDY?
NFPA 70 (NATIONAL ELECTRIC CODE) protective devices
Two standards are typically used for the IEEE C37.1
interconnection of smart devices in a IEC 61850
substation environment. One is an IEC
standard, the other is an IEEE standard.
What are the two standards?
Time travel analysis is commonly is used on medium and high-voltage circuit breakers and provides information as to
performed on: whether the breaker's operating mechanism is operating properly (NFPA 70B).
https://quizlet.com/457015131/neta-level-ii-exam-flash-cards/ 2/7