ICC California UST Inspector Exam
NEWEST 2025/2026 ACTUAL EXAM
COMPLETE QUESTIONS AND WELL
VERIFIED -ANSWER--S /ALREADY
GRADED A+ REAL 2025 EXAM
All of the following is required to be included in an UST written
monitoring procedure, EXCEPT:
a. The methods and equipment, identified by name and model
b. The names and titles of the persons responsible for monitoring
the equipment.
c. The name of the emergency coordinator
,2|Page
d. A description of the training necessary for the operation of the
tank system. ......-ANSWER--.....c. The name of the emergency
coordinator
CCR; 2632
All of the following are exempt from regulation as an UST,
EXCEPT:
a. A 1000 gallon UST on a farm
b. Drums in basements that contain 55 gallons or less
c. Liquid asphalt tank
d. A bulk field constructed UST ......-ANSWER--.....d. A bulk field
constructed UST
CCR; 2621
,3|Page
The local agency inspection is conducted to ensure that the UST is
in compliance with?
a. Title 40 CFR, Parts 280 & 281
b. Health & Safety Code, Chapter 6.11 and 23 CCR, Chapter 18
c. Title 23, Division 3, Chapter 16, Articles 3 or 4 as applicable and
with all permit conditions
d. Health & Safety Code, Chapter 6.67 and 23 CCR, Chapter 18 ......-
ANSWER--.....c. Title 23, Division 3, Chapter 16, Articles 3 or 4 as
applicable and with all permit conditions
CCR; 2712 (e)
Which of the following USTs must have evidence of financial
responsibility?
a. A UST containing sodium hydroxide
, 4|Page
b. A UST owned and operated by a State or Federal facility
c. A UST owned by the U.S. Navy
d. A County owned petroleum UST ......-ANSWER--.....d. A County
owned petroleum UST
CCR; 2711 (a)(11) and H&SC 25292.2 (careful, petroleum containing
USTs requirement is in chapter 6.75 &23 CCR, chapter 18)
All of the following are correct for single wall, pressurized, gasoline
piping after December 22, 1998, EXCEPT?
a. It must be monitored by an annual 0.1 gph test or monthly 0.2
gph test
b. It must be also be monitored by an hourly 3.0 gph test
c. The 3.0 gph monitoring shall restrict fuel flow or initiate an
alarm if an unauthorized release occurs.
d. The 3.0 gph monitoring shall shut down the pump if it fails or is
disconnected. ......-ANSWER--.....c. The 3.0 gph monitoring shall