1. The point of transfer at a dispensing unit must be a minimum of how many
feet from public ways such as streets or sidewalks?
A. 5 ft
B. 10 ft
C. 25 ft
D. 50 ft
Answer: B. 10 ft
2. Pressure relief devices for underground containers must be piped to at least
how many feet above the ground?
A. 2 ft
B. 6 ft
C. 10 ft
Answer: C. 10 ft
3. The point of transfer must be at least ___ feet from any building that is used
for public assembly.
Answer: 25 feet
4. Remote emergency shutoff devices must be:
A. Clearly labeled
B. Easily accessible
C. Located within line-of-sight when possible
, D. All of the above
Answer: D. All of the above
5. Steel supports on vertical ASME containers must be protected with fire-
resistant material rated for at least:
A. 1 hour
B. 2 hours
C. 3 hours
Answer: B. 2 hours
6. Liquid meters shall be installed in accordance with ______.
A. NFPA 54
B. NFPA 58 Chapter 14
C. NFPA 58 6.20.5.1 - ANSWER C. NFPA 58 6.20.5.1
7. T/F: The point of transfer can be located directly beneath power lines if
clearance is at least 5 feet.
Answer: False
8. What is the required minimum distance from the point of transfer to the
nearest building opening (e.g., doors, windows)?
Answer: 5 feet
9. Dispensing units must be placed so that vehicles using the unit are
positioned at least ___ feet from tanks, regulators, or relief valves.
Answer: 10 feet
10.A dispensing point located adjacent to railroad tracks must be at least ___
feet away.
Answer: 25 feet