NICET Fire Alarm Level 1 Actual Exam Preparation Newest
2025/2026 Complete 100 Questions And Correct Answers (Verified
Answers)|Already Graded A+
A riser room temperature 40 degrees F
switch should activate
when the temperature falls
below which level?
According to NFPA 72, what is 110 dBA
the
maximum sound pressure
level permitted in a space
with notification
appliances?
What is the minimum interval Annually
for testing a
single-station smoke detector
in multifamily units?
Where should a technician At the bottom of the beam
install a
detector in relation to
beam that is less than 12
inches deep and less that 8
feet in center?
An existing fire alarm cable in secured inside a listed box or enclosure
a drop
ceiling will be spliced. which
one of the
following splice locations
will comply with NFPA 70?
1/15
, 9/18/25, 8:03 PM Fire Alarm level 1
Which function shall be smoke entry?
tested for each newly
installed smoke detector?
An 180 foot long corridor is 6 heat detectors
10 feet wide, with a
smooth 10 foot ceiling,
interrupted by 4-inch beams
spaced every 10 feet. How
many heat detectors with a
listed 30 foot
spacing are required?
At which height must 7 feet
cables be physically
protected when being
installed within an exposed
ceiling?
When shall smoke After the final cleanup of all trades
detectors be installed
during the construction
process?
Where structural members 3 feet
are provided, intermediate
metal conduit shall be
secured within which
maximum distance from
an outlet box"