NICET FIRE ALARM SYSTEMS LEVEL 1
EXAM BRAND NEW OFFICIAL QUESTIONS
WITH ANSWERS.
1. A 20 foot by 20 foot room with 20 foot high ceiling requires add
a minimum a ___________ ceiling mounted strobe. - correct
answer -30 cd
2. According to NFPA 72, a 40 foot by 40 foot room or area with a
10 foot ceiling is the best covered by a _____ cd visible
notification appliance, centered on one wall. - correct answer -
60
3. Conductors returning to the fire alarm control panel from the
last field device on the circuit might indicate a _________
circuit. - correct answer -Class A
4. Secondary power supplies for an emergency voice/alarm
communications fire alarm system shall be capable of
operating for a minimum of _________ of standby followed by
__________ of alarm - correct answer -24 hour/15 minutes
, Page | 2
5. The fire alarm system primarily power branch circuit
disconnecting means must be in______ color. - correct answer
-Red
6. A secondary power supply for protected premises shall
automatically provide power within _______ seconds of the
primary power fails. - correct answer -10
7. Under which of the following conditions shall spot type smoke
detectors NOT be installed? - correct answer -When the
temperature is above 100°F.
8. Who is responsible for maintaining Personal Protective
Equipment? - correct answer -OSHA
9. What does GFCI stand for - correct answer -Ground Fault
Circuit Interrupter