QUESTIONS And CORRECT Answers
An existing system that is not in strict compliance with the provisions of this code shall be permitted to be
continued in use as long as the _ has determined that such use does not constitute a distinct hazard to life.
A) architect B) authority having jurisdiction C) engineer D) nursing staff - CORRECT
ANSWERS B) authority having jurisdiction
Cylinder and cryogenic liquid container outlet connections shall be designed as to render the attachment
point _ when removal of the outlet connection is attempted. A) reusable B) unusable C) unsuitable D)
universal - CORRECT ANSWERS B) unusable
Cylinders in use and in storage shall be prevented from reaching temperatures in excess of _ *F. A) 120
B) 125 C) 130 D) 135 - CORRECT ANSWERS B) 125
Nitrous oxide and carbon dioxide using cylinders or portable containers shall be prevented from reaching
temperatures lower than _ *F A) 130 B)125 C) 20 D) -20 - CORRECT ANSWERS C)20
Which of the following systems shall not be permitted to be located in an outdoor enclosure? A) bulk
cryogenic liquid cylinders B) manifolds for gas cylinders C) manifolds for cryogenic liquid containers D)
medical air sources - CORRECT ANSWERS D) medical air sources
Indoor locations for oxygen, nitrous oxide, and mixtures of these gases shall not communicate with any of
the following except _? A) area with open flames B) designated storage area C) engines D) kitchens -
CORRECT ANSWERS B) designated storage area
Locations for central supply systems shall have _ devices protected from physical damage? A) electrical
B) pressure indicating C) regulating D) relief - CORRECT ANSWERS A) electrical
Outdoor locations surrounded by impermeable walls, except fire barrier walls, shall have protected
ventilation openings at the _ of each wall to allow free circulation of air within the enclosure? A) base B)
corner) C) middle D) top - CORRECT ANSWERS A) base
,All positive pressure supply systems shall be provided with duplex line pressure regulators piped in _? A)
circuit B) loop C) parallel D) series - CORRECT ANSWERS C) parallel
All pressure relief valves shall be made of brass, bronze, or _? A) carbon steel B) cast iron C) copper D)
stainless steel - CORRECT ANSWERS D) stainless steel
Central supply systems for positive pressure gases shall have one or more relief valves, the valves shall
have a relief setting that is _% above normal working operating pressure? A) 30 B) 40 C) 50 D) 60 -
CORRECT ANSWERS C) 50
When vented to the outside, relief valve vent lines shall be labeled in which way? A) adhesive markers B)
any manner that will distinguish them from the medical gas pipeline C) stenciling D) stickers -
CORRECT ANSWERS B) any manner that will distinguish them from the medical gas pipeline
An auxiliary source connection shall consist of all of the following except? A) removable plug or cap B)
tee C) valve D) visual pressure indicator - CORRECT ANSWERS D) visual pressure indicator
In central supply systems using gas or liquid cylinders, each header shall have a _ to prevent debris from
entering the manifold controls? A) check valve B) filter C) monitor D) relief valve - CORRECT
ANSWERS B) filter
Manifolds for gas cylinders shall consist of two equal headers, each with enough cylinders for an average
day's supply, but not fewer than _ connections? A) 5 B) 4 C) 3 D) 2 - CORRECT ANSWERS D) 2
Manifolds for gas cylinders shall have a(n) _ signal that visibly indicates the operating status of the
equipment and shall activate an indicator at all master alarm panels when or just before changeover from
one header to the other takes place? A) area B) master C) local D) zone - CORRECT
ANSWERS C) local
When multiple buildings are served from a single cryogenic liquid oxygen source, it is required to place
the emergency oxygen supply connection in _ ? A) each building served B) the building closest to the
source C) the largest building served D) the main building only - CORRECT ANSWERS A) each
building served
, The minimum clearance around EOSC for a temporary source of supply is _ ft? A) 2 B) 3 C) 5 D) 6 -
CORRECT ANSWERS B) 3
A(n) _ emergency reserve system can be substituted for the EOSC? A) auxiliary B) backup C) in-building
D) micro-bulk - CORRECT ANSWERS C) in-building
The quality medical air shall comply with all of the following standards except? A) be filtered to .01
microns B) have less than 25 ppm gaseous hydrocarbons C) have no detectable hydrocarbons D) meet the
requirements of medical air USP - CORRECT ANSWERS A) be filtered to .01 microns
Medical air sources shall only be used for _ ? A) air-operating devices B) human respiratory applications
C) instrument air D) WAGD - CORRECT ANSWERS B) human respiratory applications
Medical air compressor systems shall have a pressure relief valve set at _ percent above line pressure? A)
20 B) 30 C) 40 D) 50 - CORRECT ANSWERS D) 50
Medical air compressor systems shall have an automatic means to prevent _ from all on-cycle
compressors through all off-cycle compressors? A) backfire B) backflow C) back pressure D) backup -
CORRECT ANSWERS B) backflow
Reciprocating compressors that employ the use of oil can be used for medical air as long as the oil-
containing section is separated from the compression chamber by at least _ seals creating an area open to
the atmosphere? A) 2 B) 3 C) 4 D) 5 - CORRECT ANSWERS A) 2
When liquid ring compressors are being used to service water and seal water shall be treated to control
waterborne pathogens and chlorine (from _) from entering the medical air? A) deionization B)
hyperchlorination C) hypochlorination D) ionization - CORRECT ANSWERS C) hypochlorination
Aftercoolers shall be provided with individual _ ? A) condensate traps B) flexible connectors C) pressure
indicators D) temperature indicators - CORRECT ANSWERS A) condensate traps