Correct Answers
Appliances installed up to 2000 feet shall be reduced how? - correct answers ✔✔4% every 1000
feet
List 3 appliances not required to be vented? - correct answers ✔✔Listed ranges, type 1 clothes
dryers and room heaters
What are the requirements for exit terminals of mechanical draft systems? - correct answers
✔✔No less than 7 feet above the floor
How high shall a chimney for a residential type extend above the highest point of the roof? -
correct answers ✔✔3 feet
What rule do you use when sizing a chimney - correct answers ✔✔7 times rule
An appliance shall not be connected to what when serving a separate appliance designed to
burn solid fuel? - correct answers ✔✔Chimney Fuel
What are the requirements when two or more openings are provided into one chimney flue? -
correct answers ✔✔They shall be at different levels
What are requirements for the installation of a cleanout? - correct answers ✔✔Shall have a
tight-fitting cover and installed 6 in below the lowest inlet.
The chimney liner shall not be used for what? - correct answers ✔✔Venting another appliance