The point of transfer at a dispensing unit must be ____ from Public ways,
including public streets, highways, thoroughfares, and sidewalks.
A. 10 feet
B. 15 feet
C. 25 feet - 🧠ANSWER ✔✔A. 10 feet
Steel supports on vertical ASME containers shall be protected against fire
exposure with a material having a fire resistance rating of a least _____,
except that continuous steel skirts that have only one opening that is 18 in.
or less in diameter shall have fire protection applied to the ______ of the
skirts.
COPYRIGHT©JOSHCLAY 2025/2026. YEAR PUBLISHED 2025. COMPANY REGISTRATION NUMBER: 619652435. TERMS OF USE. PRIVACY 1
STATEMENT. ALL RIGHTS RESERVED
, A. 3 hrs; outside
B. 2 hrs; outside
C. 3 hrs; inside - 🧠ANSWER ✔✔B. 2 hrs; outside
Pressure relief devices installed in underground containers serving
dispensing systems shall be piped vertically upward to a point at least
_____ above the ground.
A. 2 feet
B. 6 feet
C. 10 feet - 🧠ANSWER ✔✔C. 10 feet
A remote emergency shut off device for either the internal valve or
emergency shutoff valve is required to be located not less than _____ or
more than _____ from the liquid transfer point.
A. 10 ft ; 50ft
B. 10 ft; 100ft
C. 3 ft; 100ft - 🧠ANSWER ✔✔C. 3 ft; 100ft