1. 1. An oxygen deficient atmosphere is defined 20.5
as one with on oxygen percent less than
2. 2. How many fires can be lit in a four-story 1
non-gas fired burn building?
3. Pilot flames should be with the fuel Interlocked
delivery valves to prevent fuel from flowing
without confirmed pilot flame being present.
(1402 10.6.1 (C))
4. Gas detection systems should be with the Interlocked, 25%
ventilation systems and fuel delivery systems
to shupt down fuel flow and activate an exter-
nal alarm when the levels exceed LEL.
(1402 10.6.1 (D))
5. 5. Smoke used in the training facility should Non toxic and of known substance
1404 11.4)
6. 6. An Acquired Building is a structure ac- By the authority having jurisdiction from
quired a property owner for the purpose of con-
ducting live fire evolutions. (1403 3.3.2.1)
7. 7. A training center burn building is a struc- designed for conducting live fire training
ture evolutions on a repetitive basis. (1403
8. . A participant is any student, instructor, safety oflcer, vis-
itor, or person who is involved in the live
fire training evolution within the opera-
tions area.
9. Safety oflcer
1/8
, LFTI Actual Exam Questions With Reviewed 100%
Correct Detailed Answers Guaranteed Pass!!
an individual appointed by the AHJ as quali-
fied to maintain a safe working environment
at all live fire training evolutions
10. any person who is present at the live fire A student
training evolution for the purpose of receiv-
ing training. (1403 3.3.10)
11. Minimum qualification to participate in live All participates shall have had Firefighter
fire training I training
12. 2. All hazardous structural conditions shall be removed or repaired as to not present
a safety problem during use of the struc-
ture for live fire training evolutions. (1403
13. Missing stair treads and rails shall be repaired or replaced
14. Holes in walls and ceilings shall be patched
15. 15. All forms of asbestos deemed hazardous shall be removed by an approved
asbestos removal contractor. (1403
4.2.11.5)
16. Utility services adjacent to the live burn shall be removed or protected. (1403
4.2.15)
17. 17. Combustible materials, other than those shall be removed or stored in a protect-
intended for the live fire training evolution ed area to preclude accidental ignition.
(1403 4.2.17)
18. 8. The persons in charge of the adjacent shall be informed of the date and time of
properties that could be affected by the the evolution.
smoke