The "Life Safety Code" used in US hospitals is formally named - Answers NFPA 101-2012
The "Healthcare Code" used in US hospitals is formally named - Answers NFPA 99-2012
The Emergency Power (Generator) Code is formally named - Answers NFPA 110
The entity that approves respirators is - Answers NIOSH
What is the best way to identify potential workplace fire and related hazards - Answers conduct
comprehensive analyses and surveys
This is an odorless gas that inhibits the blood from carrying oxygen to the brain - Answers Carbon
Monoxide
The "Alarm System" code is formally named - Answers NFPA 72
Doors located in smoke barriers must meet what thickness and minute rating - Answers 1-3/4" thick and
a 20 minute rating
A device used in wet areas to protect humans from electric shock - Answers A ground fault circuit
interrupter (GFCI)
What type of fire extinguishing system effective on computer fires is now known to be environmentally
dangerous - Answers Halon
Which organization publishes standards specifically for bulk oxygen systems - Answers NFPA
When testing a sprinkler system how much time is allowed between achieving sustained flow and
initiation of fire alarms - Answers 90 seconds
Which agency publishes general standards on storing hazardous or flammable materials - Answers NFPA
True or False: In most situations PPE can be used as a substitute for other controls - Answers False - PPE
cannot be substituted for other appropriate controls
What is the appropriate way to detect suspected gas cylinder leaks - Answers using soapy water
OSHA and the Uniform Fire Code (UFC) define class 1 flammable liquids as any liquid with a flash point
below what temperature - Answers 73 degrees Fahrenheit
What organization addresses safety signs and color-code schemes - Answers ANSI
What fire-related injury contributes to the most fire deaths - Answers Smoke Inhalation
, What NFPA publication addresses electrical grounding requirements in healthcare facilities - Answers
NFPA 99
What NFPA standard addresses the installation of fire sprinkler systems - Answers NFPA 13
What standard or law requires healthcare facilities to develop evacuation/egress procedures for
disabled persons - Answers ADA Title III
Firewatch must be implemented when a SPRINKLER System is out of service for more than ___ hours in
a 24 hour period - Answers 10
Firewatch must be implemented when a FIRE ALARM system is out of service for more than ___ hours in
a 24 hour period - Answers 4
This code establishes the minimum fire and egress standards for buildings - Answers NFPA 101 "The Life
Safety Code"
How often must a hospital test automatic smoke detection devices for air handling equipment - Answers
Annually (also called HVAC Shutdown)
What standard addresses the requirement for testing roof hatches - Answers NFPA 72
How often do standpipe hoses need to be fully inspected
(according to NFPA 1962) - Answers Every 3 Years
Which NFPA standard addresses the placement of smoke detectors in corridors - Answers NFPA 72
Fire and Smoke doors cannot exceed what undercut gap? - Answers 3/4"
Fire and Smoke doors cannot exceed what vertical gap? - Answers 1/8"
True or False: Fire AND Smoke doors must be positive latching? - Answers False, only Fire rated doors
are required to be positive latching
True or False: Fire and Smoke doors must be self-closing? - Answers True, both fire and smoke doors
must be normally closed or automatically close in case of fire.
What NFPA publication contains detailed information about the maintenance of (non-stored)
emergency power systems? - Answers NFPA 110
Occupancy separations, such as one for business, are permitted provided the services are separated by a
____ hour separation. - Answers 2
How often must the BBI and PFI of the statement of conditions be updated to meet Joint Commission
requirements? - Answers BBI= annually and PFIs are no longer allowed. The Safer Matrix is the new
norm and See It Cite It is the program motto.