MEDICAL GAS PRACTICE TEST 2 EXAM
QUESTIONS WITH CORRECT ANSWERS
Those sections (or portions) of the piping system that serve a room, or group of rooms,
on the same story of a facility. This is the definition of which of the following. - Answer-
Branch lateral lines

A low pressure vacuum insulated vessel containing gases in liquid form. This is an
NFPA 99 definition for which of the following: - Answer-Container

Compressed Gas cylinders must meet which of the following criteria in order to be
acceptable for use in an acute Healthcare facility: - Answer-Be appropriately identified
by attached labels or stencils in accordance with CGA-C7 criteria

According to the NFPA, an oxygen enriched atmosphere is one where the concentration
of oxygen exceeds what percentage? - Answer-23.5%

Which of the following is true of category 1 support gases: - Answer-Permitted to power
medical-surgical tools

A facility is in the planning stages of installing an Emergency Oxygen Service
connection. (EOSC). What minimum clearance is required around it for the connections
of temporary auxiliary source? - Answer-3 feet

Which of the following conditions must be met when medical gas and vacuum systems
are installed by not certified personnel? - Answer-Installation by anyone other than 6010
certified personnel is not permitted.

Wooden racks for cylinder storage may be permitted under which conditions: - Answer-
Wooden racks are no longer permitted

Oxygen cylinders in use in storage shall be prevented from reaching what temperatures
in how many degrees Fahrenheit? - Answer-125°

Which of the following systems shall not be permitted to be located in an outdoor
enclosure: - Answer-medical air compressor supply sources

Metallic flexible joints are being used in the pipelines for a vibration control. Which of the
following is not required for such joints: - Answer-suitable for service at 150 PSIG or
above

Who shall witness the installer perform standing vacuum test: - Answer-The Authority
has the jurisdiction or its designee

, The medical air compressor intake shall be located at a minimum of how many feet from
any exhaust or plumbing vents - Answer-25 ft

If an in-building emergency reserve system is provided as a substitute for the EOSC, it
shall be located in a room or enclosure constructed with materials rated such that all
walls and floors are a minimum of ______
fire resistance - Answer-1 hour

The gas produced by evaporation from a secondary header in a cryogenetics liquid
cylinder system shall enter the supply system _____
of the final line regulator - Answer-Upstream

With the approval of the authority having jurisdiction in which areas shall zone valves be
permitted to be secured to prevent appropriate access. - Answer-Pediatrics &
psychiatric

Which of these operations would not breach the vacuum system? - Answer-testing a
system component with a leak detectant solution

Except for valves in zone valve boxes, all the valves shall be located in secured areas
such as locked piped chase or be: - Answer-latched or locked in operating position

An existing system that is not in strict compliance with the provisions of the standard,
shall be permitted to be continued in use as long as which of the following conditions is
met: - Answer-The authority having jurisdiction has determined that such use does not
constitute a distinct hazard to life

Medical gas supply systems are not permitted to be located where? - Answer-in an
unlocked location

Fittings, valves, and other components for oxygen used in a category 1 distribution
system, shall be _____
until prepared for installation. - Answer-Delivered, sealed, labeled, and kept sealed

Vacuum piping for ______ shall be connected separately from the medical-surgical
system directed to the receiver tank through its own isolation valve and fluid traffic
located at the receiver - Answer-a teaching Laboratory

NFPA 99 specifies that the medical gas piping system shall be protected against all
except for which of the following: - Answer-physical damage

Level One support gases carry which of these additional hazards: - Answer-higher
pressures

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
biggdreamer Havard School
View profile
Follow You need to be logged in order to follow users or courses
Sold
247
Member since
2 year
Number of followers
68
Documents
17956
Last sold
9 hours ago

4.0

38 reviews

5
22
4
4
3
6
2
2
1
4

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions