What is an installation Correct Ans-Complete and ready for operation of any oil burning
appliance
Energizing the ignition circuit during the entire burn cycle reduces Correct Ans-Ignition
component life
Fuel can be transferred from a tank to an appliance by pressurizing the tank Correct Ans-
False
What device must be equipped with an air proving switch Correct Ans-Both, draft inducers
and power-venters
What is a safety control Correct Ans-Any control used to prevent unsafe operation of the
controlled equipment
A non-resident steam or hot water boiler having a minimum safety relief valve capacity over
200,000 BTU/hr requires certificate of inspection from the department of fire services
Correct Ans-Prior to the initial firing, every 3 years after
What is the closest distance a supply tank can be to the burner Correct Ans-5 feet
Doing a combustion pretest on and oil burning appliance will not tell you anything this is why
they generally are performed Correct Ans-False
What is the minimum oil supply line size for a residential system Correct Ans-3/8 inch
A cad cell primary control can lock out safety because Correct Ans-All of the above- dirty,
faulty, not sensing flame
, Oil Burners license test with Complete Solutions
As heating oil gets colder it's viscosity thickens: Correct Ans-Increase
The main function of the primary control is: Correct Ans-Locking out on safety in the event
of flame failure
Power must be provided to an electric blower control board on terminals: Correct Ans-L1
and L2
Once a PSC motor starts Correct Ans-The centrifugal switch turns off the electricity to the
capacitor and the start windings
Materials who's electrons are so loosely bound that they can be persuaded to move with very
little pressure allowing electricity to flow are called Correct Ans-Conductors
Oil burners can make CO even when no smoke is present Correct Ans-True
Corrosion in the flu pipe may occur if Correct Ans-Flue gas temperature is below the
dewpoint and sulfur oxide's combine with water
To avoid condensing and the flu pipe and oil fired appliance should have a minimum growth
stock temperature of Correct Ans-350°F
All persons assisting and working under the supervision of a person holding a certificate as an
oil burner technician must hold current apprentice certificates issued by Department of fire
services Correct Ans-True
What size pipe is used to cross connect tank outlets piping Correct Ans-1/2 inch