100% satisfaction guarantee Immediately available after payment Both online and in PDF No strings attached 4.2 TrustPilot
logo-home
Exam (elaborations)

Journeyman Electrician Practice Test 100% ACCURATE!!

Rating
-
Sold
-
Pages
11
Grade
A+
Uploaded on
18-10-2024
Written in
2024/2025

Conductors with _____ marked on the insulation are NOT approved for use in a wet location. - ANSWERTHHN conductors with THHN insulation are approved for use in dry and damp locations only and conductors with THWN, THHW, and THW insulation are recognized for use in dry and wet locations. Given: A one-family dwelling unit with a demand load of 200 amperes is supplied with a 120/240 volt, single-phase, electrical system from the local utility company. What is the MINIMUM size aluminum THW conductors required for use as service-entrance conductors for this residence? - ANSWER4/0 AWG one-family dwelling 120/240 volt, single-phase, service-entrance conductors to be sized at an ampacity of not less than 83% of the service rating. Therefore, 200 amperes x 83% = 166 amperes; size 4/0 AWG THW aluminum conductors with an allowable ampacity of 180 amperes should be selected for this dwelling. Where a 150 kVA, single-phase transformer having a secondary voltage of 120/240 is installed at a multi-family dwelling, the full-load current rating, in amperes, of the secondary is _____. - ANSWER625 amperes To find the full-load current rating of the single-phase transformer apply the single-phase current formula as shown:I = (150 kVA x 1000) / 240 volts = 15,000/240 = 625 amperes Which one of the following listed circuit breakers is NOT a standard ampere rating? - ANSWER75 amperes provide adequate vertical clearance of the conductors and prevent physical damage to the conductors and prevent persons from making accidental contact with the conductors which may create a shock hazard or electrocution. In no case shall the point of attachment of the service-drop conductors

Show more Read less
Institution
Journeyman Electrician
Course
Journeyman Electrician









Whoops! We can’t load your doc right now. Try again or contact support.

Written for

Institution
Journeyman Electrician
Course
Journeyman Electrician

Document information

Uploaded on
October 18, 2024
Number of pages
11
Written in
2024/2025
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

Content preview

Journeyman Electrician Practice Test
100% ACCURATE!!

Conductors with _____ marked on the insulation are NOT approved for use in a wet location. -
ANSWERTHHN



conductors with THHN insulation are approved for use in dry and damp locations only and
conductors with THWN, THHW, and THW insulation are recognized for use in dry and wet locations.



Given: A one-family dwelling unit with a demand load of 200 amperes is supplied with a 120/240
volt, single-phase, electrical system from the local utility company. What is the MINIMUM size
aluminum THW conductors required for use as service-entrance conductors for this residence? -
ANSWER4/0 AWG



one-family dwelling 120/240 volt, single-phase, service-entrance conductors to be sized at an
ampacity of not less than 83% of the service rating. Therefore, 200 amperes x 83% = 166 amperes;
size 4/0 AWG THW aluminum conductors with an allowable ampacity of 180 amperes should be
selected for this dwelling.



Where a 150 kVA, single-phase transformer having a secondary voltage of 120/240 is installed at a
multi-family dwelling, the full-load current rating, in amperes, of the secondary is _____. -
ANSWER625 amperes



To find the full-load current rating of the single-phase transformer apply the single-phase current
formula as shown:I = (150 kVA x 1000) / 240 volts = 15,000/240 = 625 amperes



Which one of the following listed circuit breakers is NOT a standard ampere rating? - ANSWER75
amperes

provide adequate vertical clearance of the conductors and prevent physical damage to the
conductors and prevent persons from making accidental contact with the conductors which may
create a shock hazard or electrocution. In no case shall the point of attachment of the service-drop
conductors to be less than 10 ft. above finished grade.



Why is electrical continuity required for metallic conduit? - ANSWERTo establish an effective ground-
fault path and facilitate the operation of the over-current protective device.

, Electrical continuity is required for metallic conduit to establish an effective ground-fault path and
facilitate the operation of the overcurrent protective device.



In dwelling units, receptacle outlets installed for countertop surfaces, must be located above, but
NOT more than _____ above the countertop or work surface. - ANSWER20 inches



receptacle outlets installed for countertop or work surfaces in dwelling units may be located on or
above, but not more than 20 in. above the countertop or work surface. The intent of this rule is to
eliminate the use of unsightly extension cords (which reduces the amount of usable countertop
space) on the countertop or work surface to supply cord-and-plug connected appliances. Also,
receptacles located more than 20 inches above countertops or work surfaces may interfere with the
cabinetry to be installed.



When conductors are installed in a conduit or tubing nipple of _____ or less in length, the ampacity
adjustment factors for more than three (3) current-carrying conductors in the raceway, are not
required to be applied. - ANSWER24 inches



adjustment factors for more than three (3) current-carrying conductors in raceways shall not apply
where the raceway is not more than 24 inches in length. Where more than 3 current-carrying
conductors are installed in short lengths of conduit or tubing, the heating effect caused from the
additional conductors is insignificant therefore, the allowable ampacity of the conductors is not
greatly reduced.



In compliance with the NEC, the total marked rating of a 120-volt, cord-and-plug-connected room air
conditioner shall not exceed _____ of the rating of a branch circuit when lighting units, general-use
receptacles, or other appliances are supplied from the branch circuit. - ANSWER50%



the special provisions for room air conditioners which are (1) rated not over 250-volts ac, single-
phase and (2) which are cord-and-attachment plug connected. In order to prevent overloading the
branch circuit, as per Section 40.62(C), the total rating of the A/C unit shall not exceed 50% of the
rating of a branch circuit where lighting units, general-use receptacles or appliances are also
supplied.



the standard ampere ratings for fuses and circuit breakers. A circuit breaker with an ampere rating of
75 amperes is not a standard ampere rating.

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
papersmaster01 Howard Community College
View profile
Follow You need to be logged in order to follow users or courses
Sold
277
Member since
2 year
Number of followers
106
Documents
14036
Last sold
5 hours ago
PAPERSMASTER01

On this page you will find documents , package deals, flashcards offered by seller PAPERSMASTER01.With our documents on your side you"ll be well equipped to tackle you exams and achieve the grades you need.

3.9

71 reviews

5
22
4
33
3
9
2
3
1
4

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions