Mass oil burner Exam Practice Questions and Answers (100% Pass)
What must be done before removing an oil tank and where is it obtained? -
Answer✔️✔️-permit, from the fire department
All oil tanks over ________________ must have an open air vent pipe. Minimum
pipe size of ___________. The fill pipe cannot exceed the size of vent pipe. Both
must terminate _______________? - Answer✔️✔️-10 gallons, 1 1/4", outside of
building
No more than how many gallon oil tank (1) can be exposed in a building? -
Answer✔️✔️-660 gallons
Exposed tanks ( more than 1) in a building cannot be more than how many
gallons? - Answer✔️✔️-1320
What must be done with any unused openings on an oil tank? - Answer✔️✔️-Made
vapor tight
What cannot be used for fill and vent piping? - Answer✔️✔️-Solder copper tubing
and fittings, or plastic piping.
, ©PREP4EXAMS@2024/2025 REAL EXAM DUMPS Monday@ August 5@ 2024 6@07 PM
All oil tanks with fill and vent pipes must have what type of gauging device? -
Answer✔️✔️-Visual or audible
The maximum total capacity of all the tanks located above the lowest level of a
building cannot exceed how many gallons? - Answer✔️✔️-60
The maximum total capacity of all the tanks located above the lowest level of a
building has an exception what is it? - Answer✔️✔️-A tank on slab adjacent to first
floor
Vent pipe mjst terminate at least how many feet above grade? - Answer✔️✔️-3 feet
Vent pipe must terminate ____ feet vertically and _______ horizontally from any
building opening. - Answer✔️✔️-Two, two
What mjst vent pipe have on the terminate outside of building? - Answer✔️✔️-water
tight cap
Fill and vent pipes are slopped in which direction? - Answer✔️✔️-towards tank
re fixed sash windows considered a building opening to apply to fill and vent
piping? - Answer✔️✔️-No