Heat exchanger shall be checked for Correct Answer-Cooling water flow
All alarm pilot lights should be in what state Correct Answer-Off
There are two requirements listed under pump house conditions. What
are they? Correct Answer-Ventilating louvers are free to operate and
heat pump is adequate not less than 40°F for diesel pump rooms
Weekly inspection requires verification that the pump suction discharge
and bypass valves should be fully open Correct Answer-True
When verifying the electrical system conditions, the controller pilot light
should be Correct Answer-Green
Diesel engine, fuel tank level float switch and solenoid valve operation
shall be checked Correct Answer-Weekly visual inspection
What kind of pump do you record the time to crank? Correct Answer-
Diesel
The pertinent visual observation categories is required to be inspected.
Weekly checklist are. Correct Answer-Pump, house, conditions, pump,
system, conditions, electrical systems conditions, diesel, engine system,
conditions, and steam engine conditions
, What is the purpose of inspecting the pump assembly? Correct Answer-
Appears to be an operating condition and is free from physical damage
The transfer switch normal pilot light should be Correct Answer-
Illuminated
The isolating switch for electrical pumps should be Correct Answer-
Closed
Pump packing boxes, bearings, and casings shall be checked for Correct
Answer-Overheating
The reverse phase alarm pilot light for electric pumps should be Correct
Answer-Off
The purpose of testing the pump assembly is to ensure automatic manual
operation upon demand and continuous delivery of the required system
output and additional purpose is to detect Correct Answer-Deficiencies
not evident by inspection
The normal phase rotation pilot should be Correct Answer-On
At what level should the oil level in the vertical site glass be? Correct
Answer-Normal