ICC / UST Questions With Complete Solutions | 100% Pass
Corrosion Specialist - designs and certifies cathodic protection system Secondary containment shall be constructed to contain at least the following volumes: - A. 100% of usable capacity of primary where there is only one primary is within the secondary B. 150% of the largest container if there are multiple primary containers in a single secondary Cathodic protection tester will test cathodic protection system within __ months of installation and every __ years thereafter - 6 months 3 years Spill container shall meet the following requirements: - A. If made of metal, exterior wall shall be protected from galvanic corrosion B. Shall have minimum capacity of 5 gallons (19 L) C. Shall have drain valve which allows drainage of the collected spill into the primary container or provide means to keep spill cont empt