NATE Exam: Air Conditioning and Heat Pumps (with 100% correct answers)
Which of the following factors affects a customer's level of comfort? a. Air movement b. Humidity c. Temperature d. All of the above correct answers d (All of the above: air movement, humidity, temperature) A cooling load calculation estimates the sensible heat gain of a structure. The maximum sensible capacity of a cooling-only system should be within ____% of this calculated value. a. ±10% b. +10% c. +15% d. +30% correct answers c (+15%) The maximum sensible cooling capacity of a heat pump should be within ____% of the calculated sensible heat gain of a structure with a large heating load. a. ±10% b. +15% c. -25% d. +25% correct answers d (+25%) The combined output of a heat pump and its auxiliary heat should not exceed the calculated heat loss of a home by more than ____%.
Written for
- Institution
- Nate heat pump service
- Course
- Nate heat pump service
Document information
- Uploaded on
- September 4, 2023
- Number of pages
- 28
- Written in
- 2023/2024
- Type
- Exam (elaborations)
- Contains
- Questions & answers
Subjects
-
which of the following factors affects a customer
Also available in package deal