UST ICC Inspector question and answer rated A+ 2023
UST ICC Inspector question and answer rated A+ 2023 Exterior surface of the tank shall have: - correct answer 1. Engineering standard 2. normal diameter in ft 3. normal capacity in gal 4. degree of secondary containment 5. useable capacity in gal 6. design pressure in PSIG 7. max operating temperature in F 8. Construction materials 9. year manufactured 10. identity of manufacturer Striker plates need to be: - correct answer made of steel, minimun 1/8 inch thickness (drop-tube fulfills requirement) Laminated/coated/clay - correct answer are considered single wall how often is secondary containment tested - correct answer 36 months how often is cathodic protection cert/impressed current cathodic tested - correct answer 6 months of install, 36 months after how often does an owner have to inspect while in temporary closure - correct answer 3 months when is a integrity test notification sent to local agency - correct answer 48 hours before test