1. During inspection of a new dwelling, an inspector finds a 120/240-
volt, single-phase, 3-wire service supplying a panelboard. The service
disconnecting means is installed in a detached garage, while the meter is
located on the exterior of the dwelling. The feeder conductors from the
garage panel supply the dwelling's interior panel. Which observation
most strongly indicates that the inspector should investigate whether the
dwelling panel is actually a service equipment panel or a downstream
distribution panel?
A. The panel contains both 120-volt and 240-volt circuits
B. The panel has a grounding electrode conductor connected to it
C. The neutral and equipment grounding conductors are bonded together
downstream of the service disconnect
D. The panel contains AFCI-protected branch circuits
Answer: C.
Rationale: In a typical grounded residential system, the grounded
conductor-to-equipment grounding conductor connection is made at
the service disconnecting means. Downstream panels supplied by
feeders generally require the grounded conductor to remain isolated
from the equipment grounding conductor. A downstream neutral-to-
ground bond can create objectionable current on grounding paths and
is a major inspection concern.
1
,2. An inspector examines a 200-ampere residential service and discovers
that the grounded conductor is connected to the service equipment
enclosure by the main bonding jumper. Several branch-circuit equipment
grounding conductors are also connected to the same grounding bar.
Which statement best describes the arrangement?
A. It is always prohibited because neutral and ground must be isolated
everywhere
B. It is generally appropriate at service equipment when properly
installed
C. It is permitted only in subpanels
D. It is permitted only when the service has no grounding electrode
system
Answer: B.
Rationale: At service equipment, the grounded conductor is
intentionally bonded to the equipment grounding system through the
main bonding jumper. This establishes the effective ground-fault
current path back to the source. The important distinction is between
service equipment and downstream panelboards.
3. A residential kitchen contains a 20-ampere small-appliance branch
circuit supplying countertop receptacles. The circuit also supplies a
receptacle located inside a pantry adjacent to the kitchen. The inspector
questions the installation. What is the primary concern?
A. The pantry receptacle must always be supplied by a 15-ampere circuit
B. Small-appliance branch-circuit limitations and permitted outlets must
be evaluated
C. Pantry receptacles are never permitted
D. The kitchen must have a dedicated 30-ampere receptacle circuit
2
,Answer: B.
Rationale: Dwelling-unit small-appliance branch circuits have specific
requirements concerning the outlets they are permitted to supply. An
inspector must determine whether the pantry receptacle falls within
the permitted scope of the small-appliance branch circuit rather than
automatically assuming every nearby receptacle is acceptable.
4. A 120-volt, 20-ampere bathroom receptacle circuit supplies
receptacles in two bathrooms. A homeowner also connected a lighting
outlet in one bathroom to the same circuit. Which issue should receive
the closest inspection attention?
A. Whether bathroom receptacles are tamper-resistant
B. Whether the branch circuit is being used only for permitted bathroom
loads
C. Whether the bathroom light is controlled by a dimmer
D. Whether the circuit uses copper rather than aluminum
Answer: B.
Rationale: Bathroom branch-circuit requirements contain specific
rules governing what loads may be supplied. Inspectors should
distinguish between a circuit supplying receptacle outlets in multiple
bathrooms and a circuit supplying other loads within a bathroom. The
exact configuration must be evaluated against the applicable NEC
provisions and adopted local requirements.
5. A residential panelboard has a 40-ampere, 2-pole breaker supplying a
range. The branch-circuit conductors are rated 40 amperes, but the
equipment grounding conductor appears substantially smaller than
expected. What should the inspector determine first?
3
, A. Whether the grounding conductor is sized according to the
overcurrent protective device and applicable rules
B. Whether the range manufacturer recommends a larger neutral
C. Whether the range has a clock
D. Whether the panelboard is painted
Answer: A.
Rationale: Equipment grounding conductors are generally sized based
on the rating of the circuit's overcurrent protective device and the
applicable code provisions. The inspector should verify conductor size,
breaker rating, wiring method, and any applicable adjustment or
special requirements rather than judging the grounding conductor
solely by visual proportion.
6. An inspector finds a 14 AWG copper conductor protected by a 20-
ampere circuit breaker in a residential branch circuit. No special
condition appears to justify the arrangement. What is the most
appropriate conclusion?
A. It is generally acceptable because copper has low resistance
B. It is generally acceptable if the circuit is less than 50 feet
C. It is generally not acceptable because the conductor ampacity is
ordinarily insufficient for a 20-ampere overcurrent device
D. It is acceptable if the receptacles are 15 amperes
Answer: C.
Rationale: Under ordinary conditions, 14 AWG copper conductors are
associated with 15-ampere overcurrent protection. A 20-ampere
breaker protecting a conductor that cannot support that rating creates
an overcurrent protection mismatch. Inspectors should verify
conductor type, insulation rating, terminal limitations, and applicable
exceptions before making the final determination.
4
INSPECTOR EXAMINATION WITH ACTUAL
QUESTIONS AND VERIFIED ANSWERS,
PLUS EXPLAINED RATIONALES/EXPERT
VERIFIED FOR GUARANTEED 100% PASS
2026/LATEST UPDATE/INSTANT
DOWNLOAD PDF
1. During inspection of a new dwelling, an inspector finds a 120/240-
volt, single-phase, 3-wire service supplying a panelboard. The service
disconnecting means is installed in a detached garage, while the meter is
located on the exterior of the dwelling. The feeder conductors from the
garage panel supply the dwelling's interior panel. Which observation
most strongly indicates that the inspector should investigate whether the
dwelling panel is actually a service equipment panel or a downstream
distribution panel?
A. The panel contains both 120-volt and 240-volt circuits
B. The panel has a grounding electrode conductor connected to it
C. The neutral and equipment grounding conductors are bonded together
downstream of the service disconnect
D. The panel contains AFCI-protected branch circuits
Answer: C.
Rationale: In a typical grounded residential system, the grounded
conductor-to-equipment grounding conductor connection is made at
the service disconnecting means. Downstream panels supplied by
feeders generally require the grounded conductor to remain isolated
from the equipment grounding conductor. A downstream neutral-to-
ground bond can create objectionable current on grounding paths and
is a major inspection concern.
1
,2. An inspector examines a 200-ampere residential service and discovers
that the grounded conductor is connected to the service equipment
enclosure by the main bonding jumper. Several branch-circuit equipment
grounding conductors are also connected to the same grounding bar.
Which statement best describes the arrangement?
A. It is always prohibited because neutral and ground must be isolated
everywhere
B. It is generally appropriate at service equipment when properly
installed
C. It is permitted only in subpanels
D. It is permitted only when the service has no grounding electrode
system
Answer: B.
Rationale: At service equipment, the grounded conductor is
intentionally bonded to the equipment grounding system through the
main bonding jumper. This establishes the effective ground-fault
current path back to the source. The important distinction is between
service equipment and downstream panelboards.
3. A residential kitchen contains a 20-ampere small-appliance branch
circuit supplying countertop receptacles. The circuit also supplies a
receptacle located inside a pantry adjacent to the kitchen. The inspector
questions the installation. What is the primary concern?
A. The pantry receptacle must always be supplied by a 15-ampere circuit
B. Small-appliance branch-circuit limitations and permitted outlets must
be evaluated
C. Pantry receptacles are never permitted
D. The kitchen must have a dedicated 30-ampere receptacle circuit
2
,Answer: B.
Rationale: Dwelling-unit small-appliance branch circuits have specific
requirements concerning the outlets they are permitted to supply. An
inspector must determine whether the pantry receptacle falls within
the permitted scope of the small-appliance branch circuit rather than
automatically assuming every nearby receptacle is acceptable.
4. A 120-volt, 20-ampere bathroom receptacle circuit supplies
receptacles in two bathrooms. A homeowner also connected a lighting
outlet in one bathroom to the same circuit. Which issue should receive
the closest inspection attention?
A. Whether bathroom receptacles are tamper-resistant
B. Whether the branch circuit is being used only for permitted bathroom
loads
C. Whether the bathroom light is controlled by a dimmer
D. Whether the circuit uses copper rather than aluminum
Answer: B.
Rationale: Bathroom branch-circuit requirements contain specific
rules governing what loads may be supplied. Inspectors should
distinguish between a circuit supplying receptacle outlets in multiple
bathrooms and a circuit supplying other loads within a bathroom. The
exact configuration must be evaluated against the applicable NEC
provisions and adopted local requirements.
5. A residential panelboard has a 40-ampere, 2-pole breaker supplying a
range. The branch-circuit conductors are rated 40 amperes, but the
equipment grounding conductor appears substantially smaller than
expected. What should the inspector determine first?
3
, A. Whether the grounding conductor is sized according to the
overcurrent protective device and applicable rules
B. Whether the range manufacturer recommends a larger neutral
C. Whether the range has a clock
D. Whether the panelboard is painted
Answer: A.
Rationale: Equipment grounding conductors are generally sized based
on the rating of the circuit's overcurrent protective device and the
applicable code provisions. The inspector should verify conductor size,
breaker rating, wiring method, and any applicable adjustment or
special requirements rather than judging the grounding conductor
solely by visual proportion.
6. An inspector finds a 14 AWG copper conductor protected by a 20-
ampere circuit breaker in a residential branch circuit. No special
condition appears to justify the arrangement. What is the most
appropriate conclusion?
A. It is generally acceptable because copper has low resistance
B. It is generally acceptable if the circuit is less than 50 feet
C. It is generally not acceptable because the conductor ampacity is
ordinarily insufficient for a 20-ampere overcurrent device
D. It is acceptable if the receptacles are 15 amperes
Answer: C.
Rationale: Under ordinary conditions, 14 AWG copper conductors are
associated with 15-ampere overcurrent protection. A 20-ampere
breaker protecting a conductor that cannot support that rating creates
an overcurrent protection mismatch. Inspectors should verify
conductor type, insulation rating, terminal limitations, and applicable
exceptions before making the final determination.
4