A newly installed 4160V emergency generator has an insulation
resistance value of 150 Megohms after one minute with an equipment
temperature of 32 degrees C. Is this value acceptable per NETA
standards? - ANSWER ✔✔No
NETA ATS-2017 Table 100.11
,https://testguy.net/content/240-Insulation-Resistance-Test-Values
Know the NETA-ATS Insulation Resistance tables
Which test method measures Hydrolyzable Flouride content in SF6 gas?
- ANSWER ✔✔ASTM D2284
[Standard Test Method for Acidity of Sulfur Hexafluoride]
NETA ATS-2017 Table 100.13
Know the ASTM test names what what they test
The operating speed of a protective relay is dependent on: -
ANSWER ✔✔* Spring Tension
* Armature core air gap
* Rate of flux built up
,https://en.wikipedia.org/wiki/Protective_relay#Types_according_to_const
ruction
This was originally a 'not question'. This list is not necessarily conclusive.
It's simply the 'incorrect' answers to the 'not question'.
According to IEEE C57.106, which test is recommended for routine
acceptance of new, unprocessed oil from a supplier for use in circuit
breakers? - ANSWER ✔✔ASTM D877
[Standard Test Method for Dielectric Breakdown Voltage of Insulating
Liquids Using Disk Electrodes]
https://hvtechnologies.com/which-oil-testing-standard-should-you-
choose-to-determine-dielectric-breakdown-voltage/
Know IEEE C57 information. Know ASTM tests and definitions
Meter Sockets and meter disconnect switches should generally be
connected on what side of a service disconnecting means? -
ANSWER ✔✔The line side
COPYRIGHT©PROFFKERRYMARTIN 2025/2026. YEAR PUBLISHED 2026. COMPANY REGISTRATION NUMBER: 619652435. TERMS OF USE.
PRIVACY STATEMENT. ALL RIGHTS RESERVED
, NFPA 70-2017 Article 230.82(3)
https://www.electricallicenserenewal.com/Electrical-Continuing-
Education-Courses/NEC-Content.php?sectionID=40.0
This was originally a True/False statement question. The answer stated
that the load side is wrong. The reference above seems to imply that
meter sockets and meter disconnect switches should generally be
connected on the line side.
Know NFPA 70
What size neutral resistor would be required to limit the fault current of a
13,800-480Y/277V 1500kVA Transformer to 5A? - ANSWER ✔✔55.4
Know Ohm's Law. 277 V / 5A = 55.4 ohms