QUESTION 1
According to the Canadian Electrical Code, what is the maximum distance a
receptacle outlet can be from any point along the floor line of a habitable room?
A) 1.5 meters
B) 2.0 meters
C) 2.5 meters
D) 3.0 meters
E) 4.0 meters
CORRECT ANSWER: B) 2.0 meters
RATIONALE: The Canadian Electrical Code (CEC) Section 26-704(a) requires that
receptacle outlets in habitable rooms be located so that no point along the floor
,line is more than 2.0 meters from a receptacle outlet. This ensures adequate
accessibility for connecting appliances and reduces the need for extension cords,
which poses both safety and convenience concerns in residential and commercial
spaces.
QUESTION 2
What is the proper grounding method for a metal-sheathed cable installed in dry
locations?
A) The metal sheath alone serves as the grounding conductor
B) A separate grounding conductor must always be run inside the cable
C) Grounding depends on the cable amperage rating
D) The metal sheath can serve as the grounding conductor if properly bonded
E) Grounding is not required for metal-sheathed cable
CORRECT ANSWER: D) The metal sheath can serve as the grounding conductor
if properly bonded
RATIONALE: According to CEC Section 4-022, the metal sheath of armored cable or
metal-sheathed cable may serve as the equipment grounding conductor provided
that it is properly bonded and terminated. The sheath must maintain electrical
continuity throughout its length and be securely connected at both ends to ensure
effective grounding of equipment. This is cost-effective while maintaining safety
standards.
QUESTION 3
In a three-phase delta-connected system, what is the relationship between phase
voltage and line voltage?
A) Phase voltage equals line voltage
B) Line voltage is √3 times the phase voltage
,C) Phase voltage is √3 times the line voltage
D) Line voltage is 2 times the phase voltage
E) Phase voltage is 2 times the line voltage
CORRECT ANSWER: A) Phase voltage equals line voltage
RATIONALE: In a delta connection, each phase winding is connected directly across
two line terminals. Therefore, the voltage across each phase coil is identical to the
voltage measured between any two lines (line voltage). This is a fundamental
characteristic distinguishing delta connections from wye connections, where line
voltage is √3 times phase voltage. Understanding this relationship is critical for
proper transformer and motor analysis.
QUESTION 4
What is the minimum wire size for a branch circuit in a dwelling unit with a 15-
ampere overcurrent device?
A) AWG 12
B) AWG 10
C) AWG 8
D) AWG 6
E) AWG 4
CORRECT ANSWER: A) AWG 12
RATIONALE: CEC Table 16-100 specifies that for a 15-ampere branch circuit, the
minimum conductor size is 12 AWG copper. This provides adequate ampacity and
ensures the conductor will not overheat under normal conditions. Using smaller
conductors would violate code and create fire hazards. The 12 AWG wire has an
ampacity of at least 16 amperes at 60°C, providing a safety margin above the 15-
ampere circuit rating.
, QUESTION 5
What is the purpose of a contactor in an electrical motor control circuit?
A) To measure motor current
B) To automatically disconnect power if voltage drops
C) To control the connection and disconnection of power to the motor
D) To adjust motor speed variably
E) To protect the motor from thermal overload
CORRECT ANSWER: C) To control the connection and disconnection of power
to the motor
RATIONALE: A contactor is an electromagnetically operated switch designed
specifically to control large electrical loads like motors. When the coil is energized, it
creates a magnetic field that pulls in the movable contacts, completing the circuit to
the motor. When de-energized, the contacts open, disconnecting power. Contactors
handle high-power switching that would be impractical with manual switches and
are essential components in motor starter assemblies.
QUESTION 6
According to the CEC, what is the maximum ampere rating for a general-purpose
branch circuit in a residential dwelling?
A) 10 amperes
B) 15 amperes
C) 20 amperes
D) 25 amperes
E) 30 amperes
CORRECT ANSWER: C) 20 amperes