Consider a system with 651 initiating devices. When changes are
made to the site-specific software, how many initiating devices that
are not directly affected by the change must be tested?
ANSWERS: 50
What type of fire alarm system is characterized by protected
properties and the monitoring facility being under the same
ownership?
ANSWERS: Proprietary Station
What ANSI/UL Publication is the Standard for Central Station Alarm
Services?
ANSWERS: 827
What testing frequency for control equipment unmonitored for
alarm, supervisory, trouble signals?
ANSWERS: Annually
,A ___ is a system component that accepts and displays signals from
a DACT sent over the public switched telephone network?
ANSWERS: DACR
You are inspecting smoke detectors with integral heat detectors.
The heat detector portion has a listed spacing of 50 feet. What
spacing would be required for the detectors?
ANSWERS: 50 Feet
, What type of meter is used to measure sound level of audible
notification?
ANSWERS: Sound Level Meter
Consider a household fire alarm system which transmits signals to a
remote monitoring location. The DACT test signals shall be
transmitted at least ___?
ANSWERS: Monthly
Battery calculations shall include a minimum ___% correction factor
above the calculated amp power capacity required?
ANSWERS: 25
According to NFPA 72, the term "Should" refers to ___?
ANSWERS: A Recommendation