Level I Examination Questions And
Correct Answers (Verified Answers) Plus
Rationales 2026 Q&A | Instant
Download Pdf
Question 1
What is the minimum required water supply flow duration for a light hazard
occupancy sprinkler system per NFPA 13?
A. 20 minutes
B. 30 minutes
C. 60 minutes
D. 90 minutes
Answer: B. 30 minutes. NFPA 13 (2019) Table 11.2.3.1.2 specifies minimum
durations: light hazard = 30 minutes, ordinary = 60–90 minutes depending on
density, extra high = 90–120 minutes. Light hazard is always 30 minutes.
Question 2
Which sprinkler temperature rating is most appropriate for a residential kitchen
ceiling with a maximum expected ambient temperature of 115°F?
A. 135°F
B. 155°F
C. 175°F
D. 200°F
,Answer: B. 155°F. NFPA 13 residential sprinkler temperature ratings are based
on maximum ceiling temperatures. For ambient up to 100°F use 135°F; for 101–
150°F use 155°F. Kitchen near stove may reach 115°F, so 155°F is correct.
Question 3
What is the maximum allowable spacing for standard-response upright sprinklers
in an ordinary hazard occupancy with 12-foot ceiling height and no obstructions?
A. 100 ft² per sprinkler
B. 120 ft² per sprinkler
C. 130 ft² per sprinkler
D. 150 ft² per sprinkler
Answer: C. 130 ft² per sprinkler. NFPA 13 allows maximum protection area per
sprinkler of 130 ft² for ordinary hazard (light hazard = 200 ft², extra hazard = 100
ft²). Spacing not to exceed 15 ft between sprinklers.
Question 4
A fire pump nameplate reads 500 gpm at 100 psi. What is the minimum required
net positive suction head (NPSH) for this pump per NFPA 20?
A. 10 ft
B. 15 ft
C. 20 ft
D. Determined by pump manufacturer
Answer: D. Determined by pump manufacturer. NFPA 20 requires that the pump
manufacturer provide the NPSH required curve. The system designer must
ensure available NPSH exceeds required NPSH.
Question 5
Which type of sprinkler system uses automatic sprinklers attached to a piping
system containing air under pressure, with a valve that admits water when air
,pressure drops?
A. Wet pipe
B. Dry pipe
C. Preaction
D. Deluge
Answer: B. Dry pipe. Dry pipe systems have pressurized air or nitrogen holding
back water at the dry pipe valve. When a sprinkler opens, air escapes, valve
trips, and water flows.
Question 6
For a sidewall sprinkler, what is the minimum distance from the sprinkler deflector
to the ceiling?
A. 1 inch
B. 2 inches
C. 4 inches
D. 6 inches
Answer: C. 4 inches. NFPA 13 requires sidewall sprinkler deflectors to be located
4 to 6 inches below the ceiling for standard sidewall types, unless listed
otherwise.
Question 7
What is the primary factor in determining the required water supply for a fire
sprinkler system?
A. Occupancy classification only
B. Hydraulic calculations based on density and area
C. Number of sprinklers on the system
D. Pipe material selection
Answer: B. Hydraulic calculations based on density and area. The design density
(gpm/ft²) multiplied by the design area (ft²) gives the total flow. Occupancy
classification feeds into density/area selection, but calculations are the core.
, Question 8
Which NFPA standard covers the installation of standpipe and hose systems?
A. NFPA 13
B. NFPA 14
C. NFPA 15
D. NFPA 20
Answer: B. NFPA 14. NFPA 13 is sprinklers; NFPA 14 is standpipe and hose
systems; NFPA 15 is water spray fixed systems; NFPA 20 is fire pumps.
Question 9
In a hydraulically calculated system, the minimum residual pressure at the most
remote sprinkler should be at least:
A. 7 psi
B. 10 psi
C. 15 psi
D. 20 psi
Answer: A. 7 psi. NFPA 13 requires a minimum residual pressure of 7 psi at the
hydraulically most remote sprinkler (except for residential where it's different).
This ensures adequate spray pattern.
Question 10
What is the maximum flow velocity recommended for ferrous piping in fire
sprinkler systems?
A. 10 ft/s
B. 15 ft/s
C. 20 ft/s
D. 30 ft/s