LP GAS COMPREHENSIVE TEST SCRIPT
2026 QUESTIONS WITH SOLUTIONS 100%
CORRECT.
⩥ Bathroom. Answer: NFPA pamphlet #54 states that unvented space
heaters are not to be installed in which area?
⩥ NFPA #58 as adopted by the LP Gas Board. Answer: When LP-Gas
and other compressed gases are to be stored in the same area, the
containers shall be marked according to which regulatory agency?
⩥ Cast Iron. Answer: What material may NOT be used under service
conditions for container appurtenances for LP Gas?
⩥ 250 PSIG. Answer: Container appurtenances shall have a rated
working pressure of at least what PSIG?
⩥ 12 years from manufacture date and every 10 years thereafter.
Answer: All industrial trucks, including fork lift containers in use shall
have the pressure relief valve replaced at what interval?
⩥ 60 drill size opening. Answer: Excess flow valves shall be designed to
close automatically at the rated flow of vapor or liquid specified by the
, manufacturer. Valves shall be designed with a bypass, not to exceed
what size drill opening?
⩥ To indicate the maximum filling level. Answer: What is the purpose of
a fixed liquid level gauge on containers to be filled by volume?
⩥ Container opening or to a valve or fitting which is attached directly to
container. Answer: Pressure gauges shall be installed in what part of a
LP Gas System used in a bulk plant?
⩥ 350 PSIG. Answer: Fittings used at pressures higher than container
pressure on the discharge of the liquid transfer pump shall be suitable for
a working pressure of at least how much PSIG?
⩥ 250 PSIG. Answer: Fittings used with liquid LP Gas or with vapor LP
Gas at operating pressures over 125 PSIG shall have a working pressures
of what PSIG?
⩥ 125 PSIG. Answer: Fittings for use with vapor LP Gas at pressures
not exceeding 125 PSIG shall be suitable for a working pressure of what
PSIG?
⩥ 1,750 PSIG. Answer: Hose used for LP Gas liquid transfer shall have
a bursting pressure of what PSIG?
2026 QUESTIONS WITH SOLUTIONS 100%
CORRECT.
⩥ Bathroom. Answer: NFPA pamphlet #54 states that unvented space
heaters are not to be installed in which area?
⩥ NFPA #58 as adopted by the LP Gas Board. Answer: When LP-Gas
and other compressed gases are to be stored in the same area, the
containers shall be marked according to which regulatory agency?
⩥ Cast Iron. Answer: What material may NOT be used under service
conditions for container appurtenances for LP Gas?
⩥ 250 PSIG. Answer: Container appurtenances shall have a rated
working pressure of at least what PSIG?
⩥ 12 years from manufacture date and every 10 years thereafter.
Answer: All industrial trucks, including fork lift containers in use shall
have the pressure relief valve replaced at what interval?
⩥ 60 drill size opening. Answer: Excess flow valves shall be designed to
close automatically at the rated flow of vapor or liquid specified by the
, manufacturer. Valves shall be designed with a bypass, not to exceed
what size drill opening?
⩥ To indicate the maximum filling level. Answer: What is the purpose of
a fixed liquid level gauge on containers to be filled by volume?
⩥ Container opening or to a valve or fitting which is attached directly to
container. Answer: Pressure gauges shall be installed in what part of a
LP Gas System used in a bulk plant?
⩥ 350 PSIG. Answer: Fittings used at pressures higher than container
pressure on the discharge of the liquid transfer pump shall be suitable for
a working pressure of at least how much PSIG?
⩥ 250 PSIG. Answer: Fittings used with liquid LP Gas or with vapor LP
Gas at operating pressures over 125 PSIG shall have a working pressures
of what PSIG?
⩥ 125 PSIG. Answer: Fittings for use with vapor LP Gas at pressures
not exceeding 125 PSIG shall be suitable for a working pressure of what
PSIG?
⩥ 1,750 PSIG. Answer: Hose used for LP Gas liquid transfer shall have
a bursting pressure of what PSIG?