2026 QUESTIONS WITH SOLUTIONS
GRADED A+
◍ How often should medical gas piping installer certifications be renewed.
Answer: Every five years
◍ 1. Which of the following systems shall not be permitted to be located in an
outdoor enclosure?
A. Manifolds for gas cylinders with or without reserve
B. Medical air sources
C. Bulk cryogenic liquid system
D. Manifolds for cryogenic liquid cylinders.
Answer: B. Medical air sources
◍ 2. What system is used to monitor the operation and condition of the source
supply of each medical gas and vacuum piping system?
A. Master alarm system
B. Area alarm system
C. Building management system
D. Pressure indicator system.
Answer: A. Master alarm system
◍ What code covers medical gas pipeline system standards.
Answer: CSA Z7396.1
◍ 3. What system is used to capture and carry away gases away from
anesthesia or analgesia equipment?
A. Waste anesthetic gas disposal system
B. Medical surgical vacuum
C. Mask system
, D. Terminal system.
Answer: A. Waste anesthetic gas disposal system
◍ In general, what should medical gas piping have?.
Answer: Labels for identification and warning signsIf there are any
additions to the system, whether it's piping alarms or other parts, the system
must be inspected and recertified by the independent AHJ
◍ 4. What is not part of a typical category 1 medical gas vacuum system?
A. An inlet at locations where patient suction could be
B. Patient lead
C. Pressure gauges and operating controls
D. Shutoff valves.
Answer: A. An inlet at locations where patient suction could be
◍ What gases are included under CSA Z7396.1.
Answer: OxygenMedical air Nitrous oxide Carbon dioxide Oxygen/nitrous
oxide mixtures Helium/oxygen mixtures Instrument air Nitrogen
◍ 5. What is a pneumatic terminus of a piped gas system? Other than critical
continuous duty, nonflammable medical life support type gases.
A. Compressor
B. Service inlet
C. Service outlet
D. Vacuum outlet.
Answer: C. Service outlet
◍ 6. What guide is for preparation of precautionary labeling and marking of
compressed gas containers?
A. ANSI/ ISA S-7.0.01
B. CGA V-5
C. CGA C-7
D. CGA P-2.7.
Answer: C. CGA C-7
◍ What three systems are included under this standard?.
, Answer: Medical vacuum system support suction equipment, and evacuation
procedures, a medical vacuum system does not carry, biological matter and
is classified as a dry system however, it could still carry airborne biological
hazardsA dental vacuum system, which is a wet system and carries
biological materials. A dental vacuum system must never be connected to a
medical vacuum system. An anaesthetic gas scavenging system AGSS is
using hospital anaesthesia evacuation procedures
◍ Can medical gas systems be tested together?.
Answer: No, they must be separate. Under no circumstance, may two
systems be interconnected even if it's for testing.Across connection in a
medical gas piping system could lead to permanent damage to a patient's
health or death
◍ 7. What device that automatically reduces gas under high pressure to a
usable lower working pressure?Group of answer choices
A. Final line regulator
B. Isolation valve
C. positive negative regulator
D. pressure reducing regulator.
Answer: D. pressure reducing regulator
◍ What other code or standard does CSA Z7396.1 standard reference.
Answer: CSA B51
◍ What type of copper piping is used in medical gas systems?.
Answer: Seamless copper either type L or type K in accordance with ASTM
B819-00: standard specifications for seamless copper tube for medical gas
systems.Pressure above 1275kpa and over 3 inches must be type K4 inch or
higher is generally joined by GTAW
◍ 8. Under the risk categories, what category does major injury or death to
patients or caregivers?Group of answer choices
A. 3
B. 4
C. 1
, D. 2.
Answer: C. 1
◍ What is the copper piping packed with?.
Answer: NitrogenIf there's no nitrogen release when he cut into it, it should
be inspected, and after the pipe is cut, it should be recapped
◍ Minimum pipe sizes for pressure gases, and for vacuum systems.
Answer: 1/2" for pressure gases3/4" for vacuum systems and anaesthetic gas
scavenging systems AGSS
◍ 9. The riser is the______ pipe that connects the mail line to various levels of
the facility.
A. Main
B. Branch
C. Vertical
D. Horizontal.
Answer: C. Vertical
◍ Piping requirements for oxygen or nitrous oxide transport.
Answer: Oxygen in greater concentrations than 23.5% or of nitrous oxide
must have piping with no oil or grease because that could result in a
explosion or fire
◍ 10. The main text of which contains only mandatory provisions using the
word shall to indicate the requirements of a ______ and suitable for
adoption into law. Non-mandatory provisions shall be located in an
appendix or annex are not to be considered requirement of a
A. Standard, Code
B. Code, Standard
C. Should, Standard
D. Code, Listed.
Answer: B. Code, Standard
◍ Fittings used for connecting copper pipe must:.
Answer: Be constructed from wrought copper, brass or bronzeComply with