A 10 AWG stranded copper conductor has a cross- (b) 0.011 sq in.
sectional area of ___________.
Chapter 9, Table 8
(a) 0.007 sq in.
(b) 0.011 sq in.
(c) 0.012 sq in.
(d) 0.106 sq in.
A motor terminal housing enclosing rigidly mounted (a) 1/4 in.
motor terminals shall have a minimum of _____________
between line terminals for a 230V motor. 430.12(C) and Table 430.12(C)(1)
(a) 1/4 in.
(b) 3/8 in.
(c) 1/2 in.
(d) 5/8 in.
NATIONAL ELECTRICAL CODE EXAM.pdf NATIONAL ELECTRICAL CODE EXAM NATIONAL ELECTRICAL CODE EXAM.pdf
, NATIONAL ELECTRICAL CODE EXAM.pdf NATIONAL ELECTRICAL CODE EXAM.pdf NATIONAL ELECTRICAL CODE EXAM.pdf
Surface-mounted luminaires with a ballast shall have a (c) 410.136(B)
minimum clearance of ___________ from combustible low-
density cellulose fiberboard, unless the luminaires is 410.136 Luminaire Mounting.
marked for surface mounting on combustible low-density (B) Combustible Low-Density Cellulose Fiberboard. Where a surface-mounted
cellulose fiberboard. luminaire containing a ballast, transformer, LED driver, or power supply is to be
installed on combustible low-density cellulose fiberboard, it shall be marked for
(a) 1/2 in. this condition or shall be spaced not less than 38 mm (1-1⁄2 in.) from the surface
(b) 1 in. of the fiberboard. Where such luminaires are partially or wholly recessed, the
(c) 1-1/2 in. provisions of 410.110 through 410.122 shall apply.
(d) 2 in.
Dry-type transformers installed indoors rated over (c) 35,000V
___________ shall be installed in a vault.
450.21 Dry-Type Transformers Installed Indoors.
(a) 1,000V (C) Over 35,000 Volts. Dry-type transformers rated over
(b) 20,000V 35,000 volts shall be installed in a vault complying with Part III of this article.
(c) 35,000V
(d) 50,000V