MED GAS TEST

Central Supply systems for positive pressure gases shall have one or more relief
valves, the valves shall have a relief setting that is ____% above normal operating
pressure = - answer50%

when vented to the outside, relief valve vent lines shall be labeled in which way? -
answerany mater that will distinguish them from medical gas pipeline

an auxiliary source connection shall consist of all the following except. - answera.
removable plug or cap
b. tee
c. valve
****d. visual pressure indicator

in central supply systems using gas or liquid cylinders, each header shall have a
_______ to prevent debris from entering the manifold control. - answer filter

manifolds for gas cylinders shall consist of two equal headers, each header with enough
cylinders for an average day supply, but not fewer than ______ connections - answer2

manifolds for gas cylinders shall have a ______ signal that visibly indicates the
operating status of the equipment and shall have an indicator at all master alarm panels
when or just before the change over from one header to the other takes place -
answerlocal

when multiple buildings are served from a single cryogenic liquid oxygen source, it is
required to place the emergency oxygen supply connection in - answereach building
served

the minimal clearance around the EOSC for a temporary source of supply is _____ feet
- answer3

a _______ emergency reserve system can be substituted for the EOSC - answerin-
building

how many egress gates are required for outdoor enclosures containing bulk cryogenic
liquid systems? - answer2

an EOSC shall be installed on the exterior of the building being served. it shall be
protected from physical damage and with a minimum clearance around the connection
of _______ - answer3 feet

,the NFPA 99 has four relevant patent categories for medical gases, determined and
defined by the risk assessment. which four best describes the categories? -
answerdeath or major injury, minor injury, patient discomfort, and no impact

alternate systems, methods, or devices approved as equivalent shelled be approved by
- answerAHJ (authority having jurisdiction)

which of these is a requirement for both the primary and secondary headers for
manifolds which contain cryogenic liquid? - answerlocated in same inclosure

which area may be acceptable to communicate with an indoor central supply location of
oxygen, nitrous oxide, or a mixture of these gases? - answeran in-building emergency
reserve system

which of the following is an NFPA requirement for electrical devices in locations where
medical gas cylinders are stored? - answerdevices must be protected from physical
damage

in those portions of systems intended to handle oxygen at gage pressures greater than
_____ PSI, interconnecting the hose shall contain NO polymeric materials - answer350

why does the NFPA require a minimum clearance around an EOSC? - answerfor the
temporary connection of source supply

which of these is a requirement for the control equipment of a bulk system that is
installed physical remote from the source of supply? - answerability to locked and
secured

mainfolds for gas cylinders shall include a ______ means for alternating the two
headers from primary to secondary - answerautomatic

which of the following are medical support gases? - answernitrogen and instrument air

a factory assembled product designed for aesthetics or convenience that contains
medical gas or vacuum outlets, piping, or other devices related to medical gases. this is
a definition of which of the following? - answermanufactured assembly

the piping that connects the source (pumps, receivers, etc) to the risers or branches or
both. this is a definition of what? - answermain lines

which of the following is a device for connecting the outlets of one or more gas cylinders
to the central piping system? - answermanifold

which is NOT part of the manifold system? - answer*****a. instrument air outlet
b. valve
c. regulator

, d. pigtail

NFPA 99 design requirements for duplexed line pressure regulators piped in parallel for
the following benefits - answereither regulator can be serviced without interrupting line
service

locations for central supply and the storage of positive pressure gases if stored outside
and the area of storage is greater than 200 square feet shall have how many
entry/exits? - answer2

medical air supply systems that operate at different pressures shall be provided with? -
answerpressure regulator

all positive pressure supply systems shall be provided with the means to control the final
line pressure at the source and include _____ - answerprotection against overpressure

a bulk cryogenic supply system shall be designed redundant for service, as to maintain
normal operation while being serviced. they shall also be of a? - answerbalanced design

doors for central supply systems and storage facilities of all positive pressure gases
shall have a fire rating of how many hours? - answer3/4 hour

if an in-building emergency reserve system is provided as a substitute EOSC, it shall be
located in a room or enclosure constructed of materials rated such that all walls, floors,
ceilings are a minimum of what fire rating? - answer1 hour

if heat is required for central supply system rooms, what is the maximum allowable
temperature of the heating element? - answer266 F

A ______ system is an assembly of equipment (storage containers, regulators, relief
devices, vaporizers, manifolds, piping, etc) that has a storage capacity of more than
20,000 cubic ft. (at normal temp and pressure) including unconnected reserves on hand
at the site - answerbulk oxygen

what does it mean when the item is "listed"? - answerthey are included in a list
published by an organization that is acceptable to the AHJ

the horizontal perimeter of the patient care vicinity space extends how far from the bed?
- answer6 feet

the "area of administration" is defined as any point in a room within _____ feet of
oxygen equipment or an enclosure (hyper/hypobaric) where oxygen can be
administered - answer15 feet

category 1 medical-surgical vacuum sources shall, at a minimum, consist of ___ or
more vacuum pumps. - answer2

Document information

Uploaded on
May 15, 2026
Number of pages
17
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers
$17.99

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
julianah420
4.2
(157)
Sold
712
Followers
328
Items
35903
Last sold
3 days ago



Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions