If combination audible/ visible appliances are installed, the
location of the installed appliance shall be determined by the
requirements of the _____. -
correct answer ✅the visible appliance.
The maximum number of 12- gauge THHN wires that can be
installed in 1-inch EMT. -
correct answer ✅26
Two resistors are connected in parallel. R1= 300 Ohms, R2=300
Ohms. What is their equivalent resistance? -
correct answer ✅150 Ohms
According to NFPA 72, visible notification appliances in non-
sleeping areas must be mounted ____________ above the finished
floor. -
correct answer ✅between 80 and 96 inches
If fire alarm system impairment occurs, the owner must be notified
in writing within _____. -
correct answer ✅24 hours
, NICET LVL 1 SG EXAM QUESTIONS
AND ANSWERS
For visual notification, a 20x20 room with a 20 foot ceiling height
requires at minimum a ______ ceiling mounted strobe. -
correct answer ✅30 candella
A 40x40 area with a 10 foot ceiling is best served by a _____ visible
notification appliance, centered on one wall. -
correct answer ✅60 candella
Conductors returning to the fire alarm panel from the last field
device suggests the circuit is wired as _____. -
correct answer ✅Class A
Secondary power supply for a emergency voice/ alarm
communications fire alarm system shall be capable of operating for
a minimum of _____ in standby followed by ____ in alarm. -
correct answer ✅24 hours/ 15 minutes
Secondary power supplies shall automatically provide power within
_____ of primary power failure. -
correct answer ✅10 seconds
AND ANSWERS
If combination audible/ visible appliances are installed, the
location of the installed appliance shall be determined by the
requirements of the _____. -
correct answer ✅the visible appliance.
The maximum number of 12- gauge THHN wires that can be
installed in 1-inch EMT. -
correct answer ✅26
Two resistors are connected in parallel. R1= 300 Ohms, R2=300
Ohms. What is their equivalent resistance? -
correct answer ✅150 Ohms
According to NFPA 72, visible notification appliances in non-
sleeping areas must be mounted ____________ above the finished
floor. -
correct answer ✅between 80 and 96 inches
If fire alarm system impairment occurs, the owner must be notified
in writing within _____. -
correct answer ✅24 hours
, NICET LVL 1 SG EXAM QUESTIONS
AND ANSWERS
For visual notification, a 20x20 room with a 20 foot ceiling height
requires at minimum a ______ ceiling mounted strobe. -
correct answer ✅30 candella
A 40x40 area with a 10 foot ceiling is best served by a _____ visible
notification appliance, centered on one wall. -
correct answer ✅60 candella
Conductors returning to the fire alarm panel from the last field
device suggests the circuit is wired as _____. -
correct answer ✅Class A
Secondary power supply for a emergency voice/ alarm
communications fire alarm system shall be capable of operating for
a minimum of _____ in standby followed by ____ in alarm. -
correct answer ✅24 hours/ 15 minutes
Secondary power supplies shall automatically provide power within
_____ of primary power failure. -
correct answer ✅10 seconds