SOLUTIONS
◉ An individual 20A branch circuit can supply a single dwelling unit
bathroom for receptacle outlet(s) and other equipment within the
same bath-room. Answer: True
210.11(C)(3) Ex
◉ GFCI protection shall be provided for all 15A and 20A, 125V,
single-phase receptacles in dwelling unit unfinished portions or
areas of basements not intended as habitable rooms. Answer: True
210.8(A)(5)
◉ Ground-fault circuit-interrupter protection shall be provided for
outlets not exceeding 240V that supply boat hoists installed in
dwelling unit locations. Answer: True
210.8(C)
◉ Receptacle outlets in meeting room fixed walls shall be installed
in accordance with _____. Answer: 210.52(A)(1) through (A)(4)
210.71(B)(1)
,◉ Where branch-circuit wiring in a dwelling unit is modified,
replaced, or extended in any of the areas specified in 210.12(A), the
branch circuit shall be protected by a _____. Answer: a or b
210.12(D)
◉ If a 20A branch circuit supplies multiple receptacles, the
receptacles shall have an ampere rating of no less than _____. Answer:
15A
210.21(B)(3) and Table 210.21(B)(3)
◉ Where a portion of the dwelling unit basement is finished into one
or more habitable rooms, each separate unfinished portion shall
have a receptacle outlet installed. Answer: True
210.52(G)(3)
◉ All single-phase receptacles rated 150V to ground or less, 50A or
less and three-phase receptacles rated 150V to ground or less, 100A
or less installed _____ of commercial occupancies shall have GFCI
protection. Answer: all of these
210.8(B)(1), (2), and (3)
◉ All single-phase receptacles rated 150V to ground or less, 50A or
less and three-phase receptacles rated 150V to ground or less, 100A
or less installed in locker rooms with associated showering facilities
shall be GFCI protected. Answer: True
, 210.8(B)(7)
◉ Receptacle outlets can be installed below the countertop or work
surface in dwelling units when necessary for the physically
impaired, or if there is no means available to mount a receptacle
above an island or peninsular _____ in. above the countertop or work
surface. Answer: 20
210.52(C)(5) Ex
◉ In other than dwelling locations, GFCI protection is required for
all single-phase receptacles rated 150V to ground or less, 50A or less
and three-phase receptacles rated 150V to ground or less, 100A or
less in unfinished portions or areas of the basement not intended as
habitable rooms. Answer: True
210.8(B)(10)
◉ A receptacle outlet shall be installed at each dwelling unit kitchen
wall countertop and work surface space that is 12 in. or wider and
receptacle outlets shall be installed so that no point along the wall
line is more than _____ in., measured horizontally from a receptacle
outlet in that space. Answer: 24
210.52(C)(1)
◉ The receptacle outlet for a dwelling unit bathroom shall be
located on a _____ adjacent to the basin or basin countertop, on the