Which of the following is TRUE regarding a single-conversion UPS
system?
It has poor noise isolation from line to load.
It provides excellent frequency stability.
It supplies AC power directly to critical loads through a series inductor
or transformer.
It may achieve zero transfer time. - ANSWERS-It supplies AC power
directly to critical loads through a series inductor or transformer.
An engine-driven AC generator may be oversized when serving a .
farm
fire pump
HVAC system
residence - ANSWERS-fire pump
Systems installed to protect loads such as communications, ventilation,
or lighting systems that, when stopped, could create hazards or hamper
rescue or fire-fighting operations are known as .
legally required standby systems
emergency systems
life safety systems
END OF
PAGE 1
, NCCER 26403 EXAM LATEST
essential systems - ANSWERS-legally required standby systems
Which of the following can be used to determine battery capacity?
Hydrometer
Float test
Specific gravity calculation
Load test - ANSWERS-Load test
A storage battery must supply AT LEAST .
331⁄3% of the system voltage for the total load of circuits supplying
legally required standby power
671⁄3% of the system voltage for the total load of circuits supplying
legally required standby power
871⁄2% of the system voltage for the total load of circuits supplying
legally required standby power
100% of the system voltage for the total load of circuits supplying
legally required standby power - ANSWERS-871⁄2% of the system
voltage for the total load of circuits supplying legally required standby
power
Each patient bed location in a health care facility MUST be supplied by .
END OF
PAGE 2