4 Stages of combustion - CORRECT ANS✔✔1. Moisture evaporation
2. Release of combustible gases
3. Ignition of combustible gas
4. Char burning
The total energy produced by burning one pound of wood is approximately____________ - CORRE
Catalytic converters can lower the ignition temperature of wood smoke to approximately - CORREC
The proper UL Standard for chimneys used to vent wood stoves is - CORRECT ANS✔✔UL103HT
UL103HT - CORRECT ANS✔✔These requirements cover factory-built chimneys intended for ventin
fired residential-type appliances and building heating appliances
According to NFPA 211, the maximum horizontal run of a wood stove connector is limited to ______
vertical portion of the chimney above the connector. - CORRECT ANS✔✔50%
According to NFPA 211, a manual damper installed in a wood stove connector pipe cannot block m
of the connector when fully closed. - CORRECT ANS✔✔80%
According to NFPA 211, the maximum permitted chimney flue area is ______ times the appliance f
chimneys and ____ times the appliance flue collar area for interior chimneys. - CORRECT ANS✔✔
The maximum chimney offset angle permitted in the United States is __________ degrees (from ve
degrees
According to NFPA 211 and the IRC, a 3.5" brick wall with a 1" ventilated air space provides a ____
reduction - CORRECT ANS✔✔66%
According to NFPA 211 and the IRC, a 3.5" brick wall without ventilated air space provides a _____
reduction. - CORRECT ANS✔✔33%
According to NFPA 211 and the IRC, a 24 gauge sheet metal panel with a 1" ventilated air space pr
clearance reduction when used as a ceiling protector. - CORRECT ANS✔✔50%
4 Stages of combustion - CORRECT ANS✔✔1. Moisture evaporation
2. Release of combustible gases
3. Ignition of combustible gas
4. Char burning
The total energy produced by burning one pound of wood is approximately____________ - CORRE
Catalytic converters can lower the ignition temperature of wood smoke to approximately - CORREC
The proper UL Standard for chimneys used to vent wood stoves is - CORRECT ANS✔✔UL103HT
UL103HT - CORRECT ANS✔✔These requirements cover factory-built chimneys intended for ventin
fired residential-type appliances and building heating appliances
According to NFPA 211, the maximum horizontal run of a wood stove connector is limited to ______
vertical portion of the chimney above the connector. - CORRECT ANS✔✔50%
According to NFPA 211, a manual damper installed in a wood stove connector pipe cannot block m
of the connector when fully closed. - CORRECT ANS✔✔80%
According to NFPA 211, the maximum permitted chimney flue area is ______ times the appliance f
chimneys and ____ times the appliance flue collar area for interior chimneys. - CORRECT ANS✔✔
The maximum chimney offset angle permitted in the United States is __________ degrees (from ve
degrees
According to NFPA 211 and the IRC, a 3.5" brick wall with a 1" ventilated air space provides a ____
reduction - CORRECT ANS✔✔66%
According to NFPA 211 and the IRC, a 3.5" brick wall without ventilated air space provides a _____
reduction. - CORRECT ANS✔✔33%
According to NFPA 211 and the IRC, a 24 gauge sheet metal panel with a 1" ventilated air space pr
clearance reduction when used as a ceiling protector. - CORRECT ANS✔✔50%