Verified 100% Correct
How should PLFA conductors NOT be installed? - ANSWER -PLFA conductors
shall not be strapped, taped or attached to the exterior of any conduit or raceway.
What is a Plenum cable? What are its characteristics? - ANSWER -Cable that can
be installed in ducts, plenums or other spaces used for environmental air. It has
adequate fire resistance and low smoke-producing characteristics.
What is Riser cable? What are its characteristics? - ANSWER -Cable to be used in
vertical wire runs in shafts or between floors. Not to be used where Plenum cable
is required. It is capable of preventing fire from rising floor-to-floor.
What is General Purpose cable? What are its characteristics? - ANSWER -Cable
for general purpose fire alarm use. Not to be used where Plenum or Riser cable is
required. It is resistant to the spread of fire.
What 'type' shall plenum cable be? What substitutions are allowed'? - ANSWER -
Power Limited Fire Alarm Plenum (FPLP) CMP can be substituted.
What 'type' shall riser wire be? What substitutions are permitted? - ANSWER -
Power Limited Fire Alarm Riser (FPLR) CMP, FPLP, CMR can be substituted.
What 'type' shall general purpose wire be? What substitutions are permitted? -
ANSWER -Power Limited Fire Alarm (FPL) CMP, FPLP, CMR, FPLR, CMG and
CM can be substituted. (All types)
What is the maximum voltage permitted through multi-conductor NPLFA cables?
- ANSWER -150 volts
What is the voltage rating of PLFA cables? - ANSWER -Not less than 300 volts
Shall the voltage be marked on PLFA cables? - ANSWER -No, because they may
be misinterpreted and used for electrical applications.
What is a 'Rate Compensation Detector'? - ANSWER -A device that responds
when the temperature reaches a pre-determined level.
, What is a 'Rate of Rise Detector'? - ANSWER -A device that responds when the
temperature rises at a rate exceeding a pre-determined value.
What is a 'Smoke Detector?' - ANSWER -A device that detects both visible and
invisible combustion particles
Which sensor is best at detecting 'invisible' smoke particles? - ANSWER -
Ionization
Which sensor is best at detecting thick, 'visible' smoke particles? - ANSWER -
Photoelectric
What is a 'Spot Type Detector'? - ANSWER -A device in which the detecting
element is concentrated at a particular location.
What is a 'Digital Alarm Communicator Receiver'? (DACR) - ANSWER -A
system component that accepts and displays signals sent over the public phone
network from a DACT. (I.e. ADT monitoring center)
What is a 'Digital Alarm Communicator Transmitter? (DACT) - ANSWER -A
system component at the protected premises is connected to the detection devices.
It has line seizure and can connect to a OACR. (I.e. DSC Impassa)
What is an Alarm Signal? - ANSWER -A signal indicating an emergency that
requires IMMIDIATE action
What is a Supervisory Signal? - ANSWER -A signal that indicates the need for
action in connection with the SUPERVISION of fire equipment
What is a Trouble Signal? - ANSWER -A signal that indicates a FAULT with fire
equipment. It must have an audible signal, distinction from alarm signals.
Does an exterior horn for a sprinkler system need to be supervised? - ANSWER -
Yes
Does a fire hood sprinkler system in a kitchen need to be monitored by the fire
alarm system? - ANSWER -Yes
What is 'Cloud Chamber Smoke Detection'? - ANSWER -A detector that draws an
air sample into a high-humidity), low pressure chamber. The conditions in the