According to the IBC, which of the following fire alarm
systems are required in a group F occupancy. - Answer-A
manual fire alarm system with occupant notification
IBC, Fire alarm and smoke detection systems, factory
According to the IBC, shop drawings shall include -
Answer-A floor plan that indicates the use of all rooms,
annunciator, and voltage drop calculations
IBC 2015 907.1.1 - 907.1.2
The location of remotely located power supplies shall be -
Answer-Identified at the master control unit
NFPA 72 10.6.8
,2|Page
A contractor installed sprinkler heads to protect the
elevator hoistway. the sprinkler heads are rated at 150-
degrees Fahrenheit. the plans show heat detectors will be
installed in the hoistway to shut down elevator power prior
to sprinkler operation. what requirements are required for
the heat detectors? - Answer-Heat detectors shall have a
lower temperature rating than the sprinkler heads and
installed within 24 inches of each other
NFPA 72 21.4 - 21.4.2
A community college is what type of occupancy
classification? - Answer-Group B
IBC 2015, Section 302
A covered shopping center (mall) has a total floor area of
75,000 square feet. According to the IBC, what are the fire
alarm system requirements for this building? - Answer-An
emergency voice/alarm communication system shall be
provided
IBC, 402.7.4, 907.2.20
,3|Page
Which best describes the power supply requirements,
under specific conditions, that can be used as the sole
power source of a low-power radio transmitter? - Answer-A
primary, dry cell, battery
NFPA 72, 23.16 - 23.16.2
Where fire pumps are required to be monitored and a
building fire alarm system is installed, a pump running
signal shall be? - Answer-a supervisory or alarm signal
NFPA 72 23.8.5.9.1
A licensed electrician was hired to install duct detectors
mounted on the air ducts of a 5,000 CFM unit. Which of
the following statements is true? - Answer-The smoke
detector must be listed for use in air duct, the detectors
can initiate a supervisory signal and alarm signal
NFPA 72, duct detectors
, 4|Page
Record drawings, as built shall contain approval
documentation resulting from any? - Answer-Variances,
performance-based designs, and risk analysis
NFPA 72, record drawings
An electrically locked door is connected to the fire alarm
system in order to unlock in event of an alarm. The
customer has requested that a feature be added (push
button) to lock the doors even while in alarm. Is this
permitted by code? - Answer-No
NFPA 72, electrically locked doors
A pathway shall be designated as __________ when it is
not monitored for integrity. - Answer-Class E
NFPA 72, pathways
A sprinkler waterflow detector was installed on a sprinkler
branch of a low-rise apartment building. Upon testing, the
waterflow activated the alarm in 130 seconds. is this
acceptable as per NFPA 72? - Answer-No