Combustible gas indicators shall numerically display a volume scale
from zero percent to 100 percent in _____ increments. - ANSWERS-1
percent or smaller
IFGC 406.7.1.4 Combustible gas indicator.
IFGC
Gas shutoff valves shall be located in the same _____ as the
appliance. - ANSWERS-room
IFGC 409.5.1 Located within same room.
IFGC
Appliance shutoff valves shall be located within _____ feet of the
appliance. - ANSWERS-6 ft.
And shall be installed upstream from the union, connector or quick
disconnect device it serves. Such shutoff valves shall be provide with
access.
,IFGC 409.5.1 Located within the same room.
IFGC
A line pressure regulator shall be installed where the appliance is
designed to operate at a _____ pressure than the supply pressure. -
ANSWERS-lower
IFGC 410.1 Pressure regulators.
IFGC
Pressure regulators that require a vent shall be vented directly to the
_____. - ANSWERS-outdoors
The vent shall be designed to prevent the entry of insects, water or
foreign objects.
IFGC 410.3 Venting of regulators.
IFGC
Where automatic _____ are installed, they shall be listed for the
application and shall be sized and installed in accordance with the
manufacturers instructions. - ANSWERS-excess flow valves
,IFGC 410.4 Excess flow valves.
IFGC
A manual shutoff valve and an ____ shall be locate in the liquid line
between the pump and dispenser inlet where the dispenser device is
installed at a remote location and is not part of a complete storage and
dispensing unit mounted on a common base. - ANSWERS-excess
flow-control valve
IFGC 412.7.1 Valves
IFGC
Self-service LP-gas dispensing systems shall be provided with an
emergency shutoff switch located within _____ feet of, but not less
than _____ feet from dispensers. - ANSWERS-100 feet
20 feet
IFGC 412.8 Private fueling of motor vehicles.
IFGC
, Residential fueling appliances shall be listed. The capacity of a
residential fueling appliance shall not exceed _____ of natural gas. -
ANSWERS-5 standard cubic feet per minute
IFGC 413.2.2 General.
IFGC
The construction , repair, maintenance and approval of masonry
chimneys shall be regulated by the International _____ Code. -
ANSWERS-Building
IFGC 501.1 Scope.
IFGC
Counter appliances shall not be required to be _____. - ANSWERS-
vented
Review the 11 other requirements of this section.
IFGC 501.8 Appliances not required to be vented, item 7.