Signboards shall not obstruct any window or emergency exit and shall not be closer than
____ meter from electric and telephone posts and wires. correct answers 1.00m
A sign height clearance of not less than? correct answers 3.00m
For buildings abutting on RROW/streets or alleys without sidewalks or provisions therefor,
the signs shall not project more than? With a minimum height clearance of? correct answers
300mm , 5.00m
On arcaded RROW/streets, the signs shall not project more than ____ meter from the
outermost portion of the wall line of the allowed structure over the arcade. correct answers
600mm
On non-arcaded RROW/streets, signs shall not extend more than ____ meters over the
sidewalk and measured horizontally from the wall line or building line. correct answers 1.2m
What is the minimum thickness of glass for the panel more than 3mx3m? correct answers
15mm
What is the minimum thickness of glass for the panel with a dimension of 3m x 3m and
below? correct answers 12mm
What is the minimum thickness of glass for the panel with a dimension of 2.25m x 2.25m and
below? correct answers 10mm
What is the minimum thickness of glass for the panel with a dimension of 1.10m x 1.10m and
below? correct answers 8mm
What is the unit area per occupant for Treatment department? correct answers 22sqm
What is the unit area per occupant for institutional sleeping department? correct answers
11sqm
What is the unit area per occupant for nursing homes, children homes and homes for the
aged? correct answers 7.40sqm
What is the unit area per occupant for hospitals? correct answers 8.40sqm
What is the unit area per occupant for school shops, vocational institutions and laboratories?
correct answers 4.60sqm
What is the unit area per occupant for conference, exhibit, gymnasia? correct answers
1.40sqm
What is the unit area per occupant for classroom? correct answers 1.80sqm
What is the unit area per occupant for Hotels, apartments, dormitories? correct answers
18.60sqm