OIL BURNER LICENSE EXAM 2025
An indirect fired Appliance intended to supply heated air for space Heating and other
purposes but not intended for permanent installation - Correct Ans-Air heater
An electrical switch designed to prove that the proper draft has been established by the
power Venter or burner and allows the burner to operate. It will de-energize the burner
control circuit preventing the burner from operating, if the power venter or burner is not
performing to satisfaction. - Correct Ans-Air pressure switch
A primary safety control that causes the flow of fuel to be shut off upon a rise in fuel
level or upon receiving excess Fuel, and which operates before the Hazardous
discharge of fuel can occur. - Correct Ans-Anti flooding device
Appliances in which materials are heated or melted at temperatures not exceeding
600°F (316°C) and if not larger than 100 cu ft (2.8 m3) not including any blower
equipment and blower compartment. - Correct Ans-Low heat industrial Appliance
Appliances operating at over 50 PSIG (345 kPa) pressure when such Appliance is
larger than 100 cu ft (2.8 m3) in size. Aswell as other medium-heat appliances in
accordance with recognized good practice. - Correct Ans-Medium heat industrial
appliance
An industrial Appliance larger than 100 cu ft (2.8 m3) in size, and other furnaces
classified as high-heat appliances in accordance with recognized good practice. -
Correct Ans-High heat industrial Appliance
A standard form issued for use in all jurisdictions throughout the Commonwealth. -
Correct Ans-Application permit/Certificate of Completion
Unless otherwise indicated listed or approved by a nationally recognized testing
Laboratory - Correct Ans-Approved
The State Fire Marshal or his designee - Correct Ans-Authority having jurisdiction
A closed vessel in which water is heated, steam is generated, steam is superheated, or
any combination thereof, by the application of heat from combustible fuels in a self-
contained or attached furnace - Correct Ans-Boiler
A boiler for generating steam at pressures in excess of 15 psi (103 kPa) or for heating
water to a temperature in excess of 250° F (121°C) or at a pressure in excess of 160
PSI (1103 kPa) - Correct Ans-Boiler, High Pressure
OIL
, OIL
A low pressure hot water boiler having a volume not exceeding 120 gal (454 L) or a
heat input exceeding 200,000 BTU per hour (58.6 kW) or an operating temperature
exceeding 200° F (93°C) that provides hot water to be used externally to itself - Correct
Ans-Boiler hot water supply
A boiler for generating steam at pressures not in excess of 15 PSIG (103 kPa) or for
Furnishing water at a temperature not in excess of 250° F (121°C) pressure's not in
excess of 160 PSIG (1103 kPa) - Correct Ans-Boiler, low pressure
A burner equipped so that the main burner fuel may be turned on and ignited
automatically - Correct Ans-Burner automatically ignited
A burner equipped so that main burner fuel is used on only by hand and ignited under
supervision - Correct Ans-Burner manually ignited
A burner that includes a power-driven fan, blower, or other mechanism as the primary
means for supplying the air for combustion - Correct Ans-Burner Mechanical Draft Type
A burner that depends primarily upon the natural draft created in the chimney or venting
system to induce the air required for combustion into the burner - Correct Ans-Burner
Natural Draft Type
A stationary heating appliance compromising the following classifications: boilers,
central furnaces, floor furnaces, and wall furnaces. A floor-mounted unit heater to be
connected to a duct system is classified also as a central heating appliance. - Correct
Ans-Central heating Appliance
A system of piping through which oil is supplied from a separate central supply tank or
tanks to more than one building, mobile home, recreational vehicle or other structure -
Correct Ans-Centralized Oil Distribution System
A standard form issued for use in all jurisdictions throughout the Commonwealth. -
Correct Ans-Certificate of Completion
Chimneys shall extend not less than 2 feet (610 mm) higher than any portion of a
building within 10 feet (3048 mm), but shall be not less than 3 feet (914 mm) above the
highest point where the chimney passes through the roof. - Correct Ans-Chimney
The pipe that connects a fuel-burning appliance to a chimney. - Correct Ans-Chimney
Connector
The distance between a heat-producing appliance, chimney, chimney connector, vent,
vent connector, or plenum and other surfaces - Correct Ans-Clearance
OIL