1. b.) 14 x 14: What is the minimum size service opening for a whirlpool tub?
a.) 10 x 10
b.) 14 x 14
c.) 12 x 12
2. b.) 5: When installing a horizontal soil line a clothes washer branch connection
may not be connect closer than _________ feet down stream from a water closet
opening.
a.) 3
b.) 5
c.) 10
3. a.) seat: Handicapped accessible water closets height is measured from the
finished floor to the top of the _________.
a.) seat
b.) rim
c.) lid of the seat
4. In a restroom: Drinking fountains or water coolers shall not be installed _______.
5. b.) 4: A 3" p-trap shall have a maximum depth of ________ inches for the trap
seal:
a.) 2
b.) 4
c.) 6
6. a.) 18 x 18: _______ inches is the required clearance in front of a pedestal urinal?
a.) 18 x 18
b.) 21 x 21
c.) 24 x 24
7. c.) 36": The maximum spout height of a handicapped accessible drinking fountain
is?
a.) 31"
b.) 34"
c.) 36"
8. a.) 1 1/2": What is the minimum waste pipe size for a residential food waste
grinder?
, Omaha Journeyman Test
Study online at https://quizlet.com/_cvh6e4
a.) 1 1/2"
b.) 2"
c.) 3"
9. a.) 5': What is the maximum allowable length of a 2" horizontal waste arm from
the combination wye and 1/8 bend fitting to the fixture connection before a revent is
required?
a.) 5'
b.) 7'
c.) 8'
10. Always: When is a business required to allow the public access to the re-
strooms?
11. b.) Bathtub: Which of these fixtures requires an overflow?
a.) lavatory
b.) bathtub
c.) shampoo sink
12. b.) 18 x 18: The minimum size concrete pad for a two way cleanout on a building
sewer shall be?
a.) 14 x 20
b.) 18 x 18
c.) 24 x 24
13. b.) 4: A water closet in retail establishment has a fixture unit rating of
________________.
a. 3
b. 4
c. 6
14. a.) 1/16: When passing through a wood stud pvc shall be protected from punc-
ture by a minimum _________ inch thick steel plate.
a.) 1/16
b.) 1/8
c.) 3/16
15. supply with a stop: Chemical and soap dispensing equipment shall be con-
nected to an independent ___________.
16. c.) 38 to 48: The vale control area for a handicapped accessible shower is from
__________ to _________ inches above the finish floor.
, Omaha Journeyman Test
Study online at https://quizlet.com/_cvh6e4
a.) 30 to 44
b.) 32 to 50
c.) 38 to 48
17. c.) 150: Cleanouts are required on building sewers at intervals not to exceed
______ feet.
a.) 100
b.) 125
c.) 150
18. b.) 2": If a type I interceptor is 18' from the point of connection to the building
drain what is the minimum size vent required?
a.) 1 1/2"
b.) 2"
c.) 3"
19. c.) 24 inches: What is the maximum height from the rim of a wall mounted urinal
to the floor?
a.) 21 inches
b.) 22 inches
c.) 24 inches
20. c.) 1/2 inch: What is the maximum slope of a battery vented soil or waste
branch?
a.) 1/8 inch
b.) 1/4 inch
c.) 1/2 inch
21. a.) 2: A shower room having 8 multiple shower valves shall be service by a
minimum __________ inch drain.
a.) 2
b.) 3
c.) 4
22. a.) 16': If a 2 inch area drain is connected to a properly vented sanitary building
drain what is the maximum distance allowed between the building and the trap before
a vent is required?
a.) 16'
, Omaha Journeyman Test
Study online at https://quizlet.com/_cvh6e4
b.) 18'
c.) 24'
23. b.) a urinal and a lav: A partition is required between _________?
a.) a water closet and a urinal
b.) a urinal and a lav
c.) a water closet and a lav
24. c.) 60": How much space must be allowed for minimum floor turn around space
in an ADA restroom?
a.) 48"
b.) 54"
c.) 60"
25. a.) 31 inches: What is minimum required distance from the center of a water
closet to the center of a urinal?
a.) 31 inches
b.) 34 inches
c.) 36 inches
26. b.) 30 x 30": What is the minimum size measurement inside of a shower stall?
a.) 24 x 24"
b.) 30 x 30"
c.) 36 x 36"
27. c.) 2 ft: On a horizontal branch what is the maximum distance from the fixture
opening that a vent can be connected?
a.) 6 inches
b.) 1 ft
c.) 2 ft
28. c.) 4: How many inches from the side of a urinal to any wall or partition minimum?
a.) 2
b.) 3
c.) 4
29. c.) 3": How high above the flood rim of a future must a vent be extended vertically
before it can be run horizontally?
a.) 1"