CHC and CHFM Exam UPDATED ACTUAL Exam Questions and CORRECT Answers Fire protection for a new construction sleeping suite not exceeding 7500 sqft - CORRECT ANSWER - The room must have a sprinkler system and complete smoke detection OR sprinkler system with QRS or residential sprinklers Fire protection for a new construction sleeping suite greater than 7500 sqft - CORRECT ANSWER - The room mush have direct supervision AND total coverage automatic smoke detection and sprinkler system protection with QRS or residential sprinkle

Show more Read less
Institution
CHC
Course
CHC











Whoops! We can’t load your doc right now. Try again or contact support.

Written for

Institution
CHC
Course
CHC

Document information

Uploaded on
June 24, 2025
Number of pages
99
Written in
2024/2025
Type
Exam (elaborations)
Contains
Questions & answers

Content preview

CHC and CHFM Exam UPDATED
ACTUAL Exam Questions and CORRECT
Answers
Fire protection for a new construction sleeping suite not exceeding 7500 sqft - CORRECT
ANSWER - The room must have a sprinkler system and complete smoke detection OR
sprinkler system with QRS or residential sprinklers


Fire protection for a new construction sleeping suite greater than 7500 sqft - CORRECT
ANSWER - The room mush have direct supervision AND total coverage automatic smoke
detection and sprinkler system protection with QRS or residential sprinkler


Fire protection for existing construction not exceeding 5000 sqft. - CORRECT
ANSWER - The room must have automatic smoke detection



Fire protection for existing construction up to 10,000 sqft - CORRECT ANSWER -
Additional fire protection - Sprinkler protection and smoke partitions.


Fire protection for a non sleeping suite up to 12,500 sqft - CORRECT ANSWER - The
facility must have either quick response sprinklers or completed smoke detection


Fire protection for a non sleeping suite up to 15,000 sqft. - CORRECT ANSWER - The
facility must have BOTH quick response sprinklers and complete smoke detection


Where can you store up to 300 cubic feet of medical gas (12 E Cylinders) - CORRECT
ANSWER - They can be stored in a smoke zone without seperation.


Fire protection for a medical gas storage room with 300 cubic feet to 3000 cubic feet worth of
Medical Gas - CORRECT ANSWER - It is permitted in a non rated room with sprinkler
protection and clearance from combustibles

,Fire protection for a medical gas storage room with greater than 3000 cubic feet worth of
Medical Gas - CORRECT ANSWER - Permitted in 1 hour FRR enclosure with vents


A hospital and a business occupancy can be separated by this FRR - CORRECT
ANSWER - 2 hour FRR


A ambulatory care facility and a business occupancy can be separated by this FRR - CORRECT
ANSWER - 1 hour FRR



How far can a space be in a room from a exit corridor - CORRECT ANSWER - 100 feet
(Please note that it has to be 150/200 feet from the actual exit or smoke door)


How far can a space be in a room from a exit or smoke compartment door. - CORRECT
ANSWER - 200 feet if sprinklered
150 feet if non sprinklered


What FRR does linen and waste collection rooms required in Hospitals - CORRECT
ANSWER - 1 hour FRR


If a healthcare facility is above a business occupancy what do they need to be separated by? -
CORRECT ANSWER - 1 hour FRR between the healthcare and business floors


If a healthcare facility is above a mechanical equipment room what do they need to be separated
by? - CORRECT ANSWER - 2 hour FRR between the healthcare and business floors



What is the minimum ceiling height in patient areas? - CORRECT ANSWER - 7' 10"



What is the minimum ceiling height in corridors - CORRECT ANSWER - 7' 6"



What is the minimum required corridor in patient areas? - CORRECT ANSWER - 8 feet

,What is the minimum required corridor in non patient areas? - CORRECT ANSWER - 44
inches or 3.6666 feet


What is the required distance from a sprinkler to an obstruction - CORRECT ANSWER -
18 inches


A vertical exit connects 3 or less stories. What type of FRR does it need - CORRECT
ANSWER - 1 hr FRR


A vertical exit connects 4 or more stories. What type of FRR does it need - CORRECT
ANSWER - 2 hr FRR and must be supported by a structure having not less than a 2 hr
FRR


What are the FRR for a horizontal exit? - CORRECT ANSWER - 2 hr FRR and at least
one exit can not be horizontal


What are the smoke compartment rules regarding a story used by inpatients for sleeping or
treatment - CORRECT ANSWER - The smoke compartment must be separated into two
or more smoke compartments.


What is the maximum size for a smoke compartment - CORRECT ANSWER - 22,500 sqft


What are the smoke compartment rules regarding a story used by 50 or more patients -
CORRECT ANSWER - The smoke compartment must be separated into two or more
smoke compartments.


What FRR and door status must a new construction hazard room have that is greater than 100
sqft have? - CORRECT ANSWER - 1 hr FRR and door closures

, What FRR and door status must a new construction hazard room have that is between 50 sqft and
99 sqft? - CORRECT ANSWER - No FRR but must have door closures


What FRR must an existing hazard room have that is 50 sqft or greater? - CORRECT
ANSWER - 1 hour FRR barrier


What must two non sprinklered areas that are occupied be separated by - CORRECT
ANSWER - 1 hr FRR



What are the FRR rules for a soiled room? - CORRECT ANSWER - Must have a 1 hr
FRR and 3/4 hour door that is self closing


A room is currently under construction, and separated by a barrier. The side of the construction is
non sprinklered and the side of no construction is non sprinklered. What is the FRR of the barrier
- CORRECT ANSWER - 1 hr FRR


What is the maximum travel distance to a fire extinguisher for a Class A hazard - CORRECT
ANSWER - 75 feet


Fire extinguisher maintenance is required to be performed on what frequency? - CORRECT
ANSWER - Annually


If a fire extinguisher has a classification 2A-10B-C then it can be used for what fires? -
CORRECT ANSWER - Class A
Class B
Class C


How long can a preplanned sprinkler impairment last before a fire watch or other alternative
measure be enacted? - CORRECT ANSWER - 10 hours in a 24 hr period

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
MGRADES Stanford University
View profile
Follow You need to be logged in order to follow users or courses
Sold
1070
Member since
1 year
Number of followers
102
Documents
68976
Last sold
17 hours ago
MGRADES (Stanford Top Brains)

Welcome to MGRADES Exams, practices and Study materials Just think of me as the plug you will refer to your friends Me and my team will always make sure you get the best value from the exams markets. I offer the best study and exam materials for a wide range of courses and units. Make your study sessions more efficient and effective. Dive in and discover all you need to excel in your academic journey!

3.8

169 reviews

5
73
4
30
3
44
2
8
1
14

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions