TENNESSEE SEPTIC SYSTEMS
INSTALLATION STUDY GUIDE WITH
COMPLETE SOLUTIONS
When the estimated daily flow volume exceeds seven hundred fifty (750) gallons for a
single system, a properly designed dosing system shall be used for discharging septic
tank effluent into the disposal field. The Commissioner shall require design plans by a
licensed engineer. The Commissioner may also require:
Prior to design approval, a licensed engineer must agree, in writing, to
monitor the installation and construction of the system and upon
completion, provide a final set of construction as-built plans encompassing all
components of the system and certification that the installation is in accordance with the
design specifications.
Prior to design approval, it shall be the responsibility of the Department to review the
aforementioned design and notify the engineer, in writing, of
approval of the plans, denial of the plans or needed modifications to the plans.
2. When the design daily flow from a single source exceeds three thousand (3,000)
gallons per day, siphons or pumps shall be used which shall discharge to separate
disposal fields. Each system shall not exceed a design capacity of
three thousand (3,000) gallons per day.
3. Discharges from dosing systems shall be designed to maximize the distribution of the
effluent throughout the system.
4.
Buffer zones shall be required at a frequency and size as determined by a detailed
soil/site evaluation.
- ANSWER-Recirculating Design - A recirculating design provides equal distribution of
the effluent throughout the entire system by connecting successive trenches on both
ends and by maintaining the grade in the bottom of these trenches from level to no
more than four (4) inches. In this manner, the entire absorption area within the sewage
system is utilized concurrently.
- ANSWER-Serial Distribution - In serial distribution, each adjacent trench is connected
to the next
by a closed pipe laid on an undisturbed section of ground. The arrangement is such
that all effluent is discharged to the first trench until it is filled. Excess liquid is then
carried by means of a closed line (relief line) to the next trench. In this manner, each
portion of the subsurface system is used in succession.
- ANSWER-Where conventional subsurface sewage disposal systems are installed,
sufficient additional area must be available for the expansion of the disposal field in an
amount large enough to
, install a secondary subsurface sewage disposal field as defined by these regulations.
"Pressure Compensating Drip Emitters" - ANSWER-means drip emitters that discharge
water out of an orifice at a constant rate over a range of operating pressures.
"Recirculating Gravel Filter (RGF)" - ANSWER-means a type of gravel filter wastewater
treatment system that utilizes an effluent recycle system where a portion of the filtered
effluent is mixed with septic tank effluent in a recirculation/dilution tank and redistributed
to the filter.
A Chamber System - ANSWER-is a media replacement system consisting of a plastic
arch-shaped open bottomed chamber. Chamber systems that exceed seven hundred
fifty (750) gallons of estimated daily flow volume shall meet the minimum requirements
established in subparagraph (3)(c) of this rule.
2.
Site and Soil Requirements
The site and soil requirements are the same as for a conventional subsurface sewage
disposal system.
(11) An area of suitable soil must be available equivalent in size to that necessary to
install and duplicate a conventional subsurface sewage disposal system.
Layout of the Chamber System
The size of a chamber system shall be equivalent to the total linear footage required for
a three (3) feet wide conventional subsurface sewage disposal
system. However, where the soil absorption rate is from ten (10) to sixty (60) minutes
per inch, the total linear footage may be reduced by thirty (30) percent. If a portion of a
unit is left over after determining the total linear
footage required, round up to the nearest whole unit.
The location of the septic tank and the disposal field shall be in accordance with Rule
0400-48-01-11.
The lateral lines shall be placed on contour. The maximum length of a single line should
not exceed one hundred (100) feet unless conditions require a longer line.
The trench bottom of each lateral shall have a grade from level to no greater than two
(2) inches per lateral line.
A minimum of six (6) feet of undisturbed earth between adjacent trench walls shall be
required.
Trench width shall be no more than six (6) inches wider than the product width, with the
maximum trench width being thirty-six (36) inches.
Trench depth shall range from twenty-four (24) to forty-eight (48) inches.
Soil material excavated from trenches should be used in backfilling and should be left
mounded over the trenches until initial set
Commissioner - ANSWER-No system shall be covered without the inspection and
authorization of the
Construction Permit 1 - ANSWER-No property owner or installer of a subsurface
sewage disposal system shall construct, alter, extend or repair subsurface sewage
INSTALLATION STUDY GUIDE WITH
COMPLETE SOLUTIONS
When the estimated daily flow volume exceeds seven hundred fifty (750) gallons for a
single system, a properly designed dosing system shall be used for discharging septic
tank effluent into the disposal field. The Commissioner shall require design plans by a
licensed engineer. The Commissioner may also require:
Prior to design approval, a licensed engineer must agree, in writing, to
monitor the installation and construction of the system and upon
completion, provide a final set of construction as-built plans encompassing all
components of the system and certification that the installation is in accordance with the
design specifications.
Prior to design approval, it shall be the responsibility of the Department to review the
aforementioned design and notify the engineer, in writing, of
approval of the plans, denial of the plans or needed modifications to the plans.
2. When the design daily flow from a single source exceeds three thousand (3,000)
gallons per day, siphons or pumps shall be used which shall discharge to separate
disposal fields. Each system shall not exceed a design capacity of
three thousand (3,000) gallons per day.
3. Discharges from dosing systems shall be designed to maximize the distribution of the
effluent throughout the system.
4.
Buffer zones shall be required at a frequency and size as determined by a detailed
soil/site evaluation.
- ANSWER-Recirculating Design - A recirculating design provides equal distribution of
the effluent throughout the entire system by connecting successive trenches on both
ends and by maintaining the grade in the bottom of these trenches from level to no
more than four (4) inches. In this manner, the entire absorption area within the sewage
system is utilized concurrently.
- ANSWER-Serial Distribution - In serial distribution, each adjacent trench is connected
to the next
by a closed pipe laid on an undisturbed section of ground. The arrangement is such
that all effluent is discharged to the first trench until it is filled. Excess liquid is then
carried by means of a closed line (relief line) to the next trench. In this manner, each
portion of the subsurface system is used in succession.
- ANSWER-Where conventional subsurface sewage disposal systems are installed,
sufficient additional area must be available for the expansion of the disposal field in an
amount large enough to
, install a secondary subsurface sewage disposal field as defined by these regulations.
"Pressure Compensating Drip Emitters" - ANSWER-means drip emitters that discharge
water out of an orifice at a constant rate over a range of operating pressures.
"Recirculating Gravel Filter (RGF)" - ANSWER-means a type of gravel filter wastewater
treatment system that utilizes an effluent recycle system where a portion of the filtered
effluent is mixed with septic tank effluent in a recirculation/dilution tank and redistributed
to the filter.
A Chamber System - ANSWER-is a media replacement system consisting of a plastic
arch-shaped open bottomed chamber. Chamber systems that exceed seven hundred
fifty (750) gallons of estimated daily flow volume shall meet the minimum requirements
established in subparagraph (3)(c) of this rule.
2.
Site and Soil Requirements
The site and soil requirements are the same as for a conventional subsurface sewage
disposal system.
(11) An area of suitable soil must be available equivalent in size to that necessary to
install and duplicate a conventional subsurface sewage disposal system.
Layout of the Chamber System
The size of a chamber system shall be equivalent to the total linear footage required for
a three (3) feet wide conventional subsurface sewage disposal
system. However, where the soil absorption rate is from ten (10) to sixty (60) minutes
per inch, the total linear footage may be reduced by thirty (30) percent. If a portion of a
unit is left over after determining the total linear
footage required, round up to the nearest whole unit.
The location of the septic tank and the disposal field shall be in accordance with Rule
0400-48-01-11.
The lateral lines shall be placed on contour. The maximum length of a single line should
not exceed one hundred (100) feet unless conditions require a longer line.
The trench bottom of each lateral shall have a grade from level to no greater than two
(2) inches per lateral line.
A minimum of six (6) feet of undisturbed earth between adjacent trench walls shall be
required.
Trench width shall be no more than six (6) inches wider than the product width, with the
maximum trench width being thirty-six (36) inches.
Trench depth shall range from twenty-four (24) to forty-eight (48) inches.
Soil material excavated from trenches should be used in backfilling and should be left
mounded over the trenches until initial set
Commissioner - ANSWER-No system shall be covered without the inspection and
authorization of the
Construction Permit 1 - ANSWER-No property owner or installer of a subsurface
sewage disposal system shall construct, alter, extend or repair subsurface sewage